3
SPECIFICATIONS
3.4.26
When disconnection state is checked, a value stored into CH
value (Un\G11toUn\G18) is set. (Refer to Section 3.2.3)
The value to be stored is selected from "Up scale", "Down scale" or "Given value".
(1) Setting methods
Un\G164 (Disconnection state
conversion setting CH1 to CH4)
Un\G165 (Disconnection state
conversion setting CH5 to CH8)
Figure 3.39 Setting of Disconnection state conversion setting (Un\G164, Un\G165)
(2) Default value
3
- 60
3.4 Buffer Memory
3.4.26 Disconnection state conversion setting (Un\G164, Un\G165) (Q68TD-G-H01only)
Disconnection state conversion setting (Un\G164, Un\G165)
(Q68TD-G-H01only)
(a) Set the value to be stored in buffer memory.
to
b15
CH4
CH8
The value to be stored into CH
in the disconnection state check changes as follows, depending on the setting
value.
1) Up scale (0
)
H
Up-scale of the range currently set is stored.
2) Down scale (1
H
Down-scale of the range currently set is stored.
3) Given value (2
H
The value set in CH
(Un\G166toUn\G173) is stored.
(b) Turn on Operating condition setting request (Y9) to activate the setting.
All channels are set to "Down scale" (1111
POINT
If a value out of the setting range is set, the module operates with the default
setting, "Down scale"(1
to
b12 b11
b8 b7
CH3
CH7
Measured temperature value when
confirming disconnection state
Measured temperature value (Un\G11toUn\G18)
)
)
Conversion setting for disconnection state value
).
H
).
H
Measured temperature
to
b4 b3
to
CH2
CH1
CH6
CH5
Setting
value
Up scale
0
H
Down scale
1
H
Given value
2
H
b0