Troubleshooting - Mitsubishi Q68TD-G-H01 User Manual

Channel isolated thermocouple input module
Hide thumbs Also See for Q68TD-G-H01:
Table of Contents

Advertisement

8

TROUBLESHOOTING

Error
Error
Code
level
(Decimal)
The averaging count setting value set in Un\G1 to Un\G8 is
*1
Light
outside the range of 4 to 500 times.
30
indicates the channel number set incorrectly.
The moving average count setting value set in Un\G1 to Un\
*1
Light
G8 is outside the range of 2 to 60 times.
31
indicates the channel number set incorrectly.
The time constant setting value for the primary delay filter
set in Un\G1 to Un\G8 is outside the range of 320 to
*1
Light
32
5000ms.
indicates the channel number set incorrectly.
(Gain value) - (Offset value)
*1
Light
40
indicates the channel number where an error occurred.
(Gain temperature setting value) - (Offset temperature
*1
Light
setting value)
41
indicates the channel number where an error occurred.
The same channel or 0 is set to both the offset/gain setting
*1
Light
(Offset specification) (Un\G26) and offset/gain setting (Gain
500
specification) (Un\G27).
When the channel change request (YB) is turned ON, the
setting status is in the following either status.
•The offset temperature setting value or gain temperature
setting value of the specified channel is set outside the
*1
Light
51
measured range.
•The disconnected channel or the channel for conversion
disable is specified.
indicates the channel number set incorrectly.
The process alarm upper/lower limit value (Un\G94 to Un\
G125) is set contradictorily.
indicates the channel number set incorrectly.
indicates the following status.
0: The lower lower limit value is lower than the
*1
Light
6
measurement range.
1: The upper upper limit value is higher than the
measurement range.
2: (Lower lower limit value) > (Lower upper limit value)
3: (Lower upper limit value) > (Upper lower limit value)
4: (Upper lower limit value) > (Upper upper limit value)
The rate alarm warning detection period (Un\G126 to Un\
*1
Light
G133) is outside the range of 1 to 6000 times
70
indicates the channel number set incorrectly.
Wire disconnection of the cold junction temperature
*1
Middle
800
compensation resistor (RTD) is detected.
The setting value in the scaling range upper/lower limit
value (Un\G62 to Un\G77) or scaling width upper/lower limit
*1
value (Un\G78 to Un\G93) indicates that (Lower limit) =
Light
91
(Upper limit).
indicates the channel number set incorrectly.
8
- 2
8.1 Error Code List
Table 8.1 Error code list (2/2)
Description
0.1 [
]
0.1 [ ]
Remedy
Reset the average count setting value to within 4 to 500
times.
Reset the moving average count setting value to within
2 to 60 times.
Reset the time constant setting value to within 320 to
5000ms.
Check the voltage at the thermocouple input terminal.
Reset the offset/gain temperature setting value (Un\
G28 to Un\G43) of the channel number where an error
occurred.
Reset the data of the offset/gain setting (Offset
specification) (Un\G26) and offset/gain setting (Gain
specification) (Un\G27).
•Check the measurement range and reset the offset/
gain temperature setting value (Un\G28 to Un\G43)
within the range.
•Check wire disconnection or specify the channel for
conversion enable.
Reset the process alarm upper/lower limit value (Un\
G94 to Un\G125).
Reset the rate alarm warning detection period (Un\
G126 to Un\G133) to within 1 to 6000 times.
Check wiring status of the cold junction temperature
compensation resistor (RTD).
Reset the scaling range upper/lower limit value (Un\
G62 to Un\G77) or scaling width upper/lower limit value
(Un\G78 to Un\G93).