Ch[ ] Time/Count/Moving Average/Time Constant Setting (Un\G1 To Un\G8) - Mitsubishi Q68TD-G-H01 User Manual

Channel isolated thermocouple input module
Hide thumbs Also See for Q68TD-G-H01:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.3
CH[ ] Time/Count/Moving average/Time constant setting (Un\G1 to
Un\G8)
When the averaging processing (1
selection (Un\G24, Un\G25), time average, count average, moving average or time
constant for primary delay filter is set. (Refer to Section 3.2.1)
(1) Setting methods
(a) Set the following setting range in buffer memory.
(b) Turn on Operating condition setting request (Y9) to activate the setting. (Refer to
(2) Default value
All channels are set to "0".
POINT

3.4.3 CH[ ] Time/Count/Moving average/Time constant setting (Un\G1 to Un\G8)

Table 3.10 Settable range
Processing method
Time average
Count average
Moving average
Primary delay filter
* 1 Set the values in units of 320ms.
For the details of the setting values, refer to Section 3.2.1 (3) Averaging processing or Section
3.2.1 (4) Primary delay filter.
Section 3.3.2)
(1) When a value out of the setting range in Table 3.10 is written, an error occurs
and the following also occurs.
• The error codes (20 , 30 , 31 , 32 ) are stored to the error code
(Un\G19). (Refer to Section 8.1)
• Error flag (XF) turns on.
• Conversion processing is performed with the setting before the error
occurence.
(2) When a value is set on the channels set sampling processing (0
Averaging processing selection (Un\G24, Un\G25), the setting value of CH
Time/Count/Moving average/Time constant setting (Un\G1 to Un\G8) is
ignored.
to 4
) is specified with Averaging processing
H
H
Setting value
*1
1280 to 5000(ms)
4 to 500(times)
2 to 60(times)
*1
320 to 5000(ms)
3.4 Buffer Memory
1
2
3
4
5
6
) to
H
7
8
3