Operation

8.6 Communication via PROFINET IO

8.6
Communication via PROFINET IO
8.6.1

Establishing online operation: STARTER via PROFINET IO

Description
The following options are available for online operation via PROFINET IO:
● Online operation via IP
Requirements
● STARTER with Version ≥ 4.1.5 (SINAMICS DCP is only supported as of STARTER
Version 4.1.5)
● CBE20
STARTER via PROFINET IO (example)
Image 8-40
Procedure for establishing online operation with PROFINET
1. Setting the IP address in Windows
Assign the PG/PC a fixed, free IP address. In our example, we selected 169.254.11.1,
based on the factory setting of the integrated EtherNet interface X127 (169.254.11.22).
Set the subnet mask to 255.255.0.0.
2. Settings in STARTER.
3. Enter the IP address and a name for the drive unit's PROFINET interface.
The PROFIBUS interface must be "initialized" so that STARTER can establish
communication.
4. Select online operation in STARTER.