8.5.3.4

Diagnostics options

The standard slave diagnostics can be read online in the HW Config.
8.5.3.5

SIMATIC HMI addressing

You can use a SIMATIC HMI as a PROFIBUS master (master class 2) to access SINAMICS
directly. With respect to SIMATIC HMI, SINAMICS behaves like a SIMATIC S7. For
accessing drive parameters, the following simple rule applies:
● Parameter number = data block number
● Parameter subindex = bit 0 ... 9 of data block offset
● Drive object number = bit 10 ... 15 of data block offset
Pro Tool and WinCC flexible
The SIMATIC HMI can be configured flexibly with "Pro Tool" or "WinCC flexible".
The following specific settings for drives must be observed when configuration is carried out
with Pro Tool or WinCC flexible.
Controllers: Protocol always "SIMATIC S7 - 300/400"
Table 8- 26
Field
Network parameter profile
Network parameter baud rate
Communication partner address
Communication partner
slot/rack
Table 8- 27
Field
Name
Controller
Type
Range
DB
(data block number)
SINAMICS DCP
Operating Instructions, 05/2016, A5E34382853K
Additional parameters
Variables: "General" tab
8.5 Communication via PROFIBUS DP
Value
DP
Any
PROFIBUS address of the drive unit
don't care, 0
Value
Any
Any
Depending on the addressed parameter value,
e.g.:
INT: for integer 16
DINT: for integer 32
WORD: for unsigned 16
REAL: for float
DB
Parameter number
1 ... 65535
Operation
171