Length
Notes:
1. The cabinet and module ground wire specification is #10 AWG insulated green safety
ground wire.
2. The cabinet conduit can be 19.1 mm (0.75-in.) or 31.8 mm (1.25-in.), and must be
insulated from the cabinet ground.

Metric wire conversion

AWG No.
2
4
6
8
10
12
14
16
18
20
22

DC rack cabling

The following photograph shows typical rack power cabling:
®
Avaya CallPilot
1002rp Server Hardware Installation
#10 AWG
Industry standard nominal
(sq mm)
35
25
16
10
6
4
2.5
1.5
1
0.75
0.5
#8 AWG
#6 AWG
Resistance at 20 C (Ohm/100 m)
0.05
0.08
0.13
0.20
0.33
0.63
1.00
1.40
2.00
2.90
4.60
Metric wire conversion
Junction
Junction
box #4
box #4
AWG
AWG
December 2010
37