Page 6
GEM-RP1CAe2/GEM-K1CA Keypad Easy Program Menu
o create a custom program using the GEM-RP1CAe2/GEM-K1CA keypad, simply answer the following questions and re-
T
cord your information on the Easy Menu Programming Worksheet. In each of the following steps, press
the NEXT/YES button to go forwards, the PRIOR/NO button to go backwards,
# o f Z n s i n A r e a 1
E n t e r # Z o n e s X X
(Direct Entry)
# o f Z n s i n A r e a 2
E n t e r # Z o n e s X X
(Direct Entry)
F i r e
Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
2 - W i r e F i r e Z n s
E n t e r Z o n e #
° °
(Direct Entry)
R e p o r t A l l Z o n e s
T o C e n t r a l ? Y / N
(Press YES or NO)
E x i t / E n t r y Z o n e s
E n t e r Z o n e #
X X
(Direct Entry)
I n t e r i o r Z o n e s
E n t e r Z o n e #
X X
(Direct Entry)
2 4 H o u r Z o n e s
E n t e r Z o n e #
° °
(Direct Entry)
C h i m e Z o n e s
E n t e r Z o n e #
° °
(Direct Entry)
X
GEM-P3200 Programming Instructions
Total Number of Zones in Area 1 (New Program Only)
•
Enter the total number of zones to be programmed for Area 1.
•
Valid entries are from 08 to 48. Directly enter the total number of zones, including leading zeros.
•
The system is based on groups of 4 zones each (after the first 8 zones), and will automatically round up to
the next group of 4. For example, if you enter 18, it will automatically convert this to 20 zones. Press
save. Press the NEXT/YES button to proceed.
Total Number of Zones in Area 2 (New Program Only)
•
Enter the total number of zones to be programmed for Area 2.
•
Valid entries are from 00 to 48. Directly enter the total number of zones, including leading zeros.
•
The system is based on groups of 4 zones each (after the first 8 zones), and will automatically round up to
the next group of 4. For example, if you enter 18, it will automatically convert this to 20 zones. Press
save. Press the NEXT/YES button to proceed.
Fire Zones in Area 1 (New Program Only)
•
Enter the zone number of any Fire Zones (including 2-wire, 4-wire or wireless).
•
Valid entries are from 01 to 48.
•
Directly enter each zone number, including leading zeros, and press
additional zone(s). Press the NEXT/YES button to proceed.
2-Wire Fire Zones in Area 1 (New Program Only)
•
Enter the zone number of any Fire Zone (from previous question) to be used with 2-wire smoke detectors.
•
Valid entries are 07 and 08. Directly enter each zone number, including leading zeros.
•
U
Press
to save, and repeat for any additional zone(s); press NEXT to proceed.
NOTE: Only zones which have been designated as Fire Zones can be programmed as 2 Wire Fire zones.
JP3 must be set to "2-WF" position for 2-wire fire for zones 7-8. (refer to Installation Instructions).
Local or Central Station Reporting System (New Program Only)
Press the NEXT/YES button for all zones to report; press the PRIOR/NO button for local system.
Exit/Entry Zones in Area 1 (New Program Only)
•
Enter the zone numbers of zones to be used as Exit/Entry zones.
•
Valid entries are from 01 to 48. Directly enter each zone number, including leading zeros.
•
U
Press
to save and repeat for any additional zone(s); press the NEXT/YES button to proceed.
NOTE: Entry Delay Time of 30 seconds and Exit Delay Time of 60 seconds will automatically be programmed.
Interior Zones in Area 1 (New Program Only)
•
Enter the zone numbers to be used as Interior Zones.
•
Valid entries are from 01 to 48. Directly enter each zone number, including leading zeros.
•
U
Press
to save and then repeat for any additional zone(s).
•
Press the NEXT/YES button to proceed.
•
All Interior zones will also be automatically programmed as "Exit/Entry Follower" and as "Power Up Delay" zones.
24 Hour Zones in Area 1 (New Program Only)
•
Enter the zone numbers of zones to be used as 24 Hour zones.
•
Valid entries are from 01 to 48. Directly enter each zone number, including leading zeros.
•
U
Press
to save and repeat for any additional zone(s); press the NEXT/YES button to proceed.
NOTE: 24 Hour Zones will automatically be programmed as audible (Burg Output).
Chime Zones in Area 1 (New Program Only)
•
Enter the zone numbers which are to be used as Chime Zones.
•
Valid entries are from 01 to 48. Directly enter each zone number, including leading zeros.
•
U
Press
to save and then repeat for any additional zone(s), press the NEXT/YES button to proceed.
NOTE: A chime time of 2 seconds will be automatically programmed.
U
to save and
twice to exit at any time.
C
U
to save, and then repeat for any
L
NAPCO Security Systems
WI818G 10/05
to set cursor,
R
U
to
U