EASY MENU DRIVEN PROGRAM MODE
o create a custom program using the F-64PROG programmer, simply answer the following questions and record your infor-
T
mation on the Easy Menu Programming Worksheet (see page 44). In each of the following steps, press
NEXT/YES button to go forwards, the PRIOR/NO button to go backwards,
# o f Z n s i n A r e a 1
E n t e r # Z o n e s X X
(Direct Entry)
E Z Z o n e D o u b l i n g
E n a b l e d ?
Y / N
(Press YES or NO)
F i r e
Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
2 - W i r e F i r e Z n s
E n t e r Z o n e #
(Direct Entry)
R e p o r t A l l Z o n e s
T o C e n t r a l ? Y / N
(Press YES or NO)
E x i t / E n t r y Z o n e s
E n t e r Z o n e #
(Direct Entry)
I n t e r i o r Z o n e s
E n t e r Z o n e #
(Direct Entry)
2 4 H o u r Z o n e s
E n t e r Z o n e #
(Direct Entry)
Freedom F-64 Programming Instructions
Total Number of Zones in Area 1 (New Program Only)
Enter the total number of zones to be programmed for Area 1.
Valid entries are from 01 to 64. Directly enter the total number of zones, including leading zeros.
The system is based on groups of 4 zones each (after the first 8 zones), and will automatically
round up to the next group of 4. For example, if you enter 18, it will automatically convert this to
20 zones. Press
Panel Zone Doubling (New Program Only)
To double the number of hardwired panel zones from 8 to 16, press YES.
If Panel Zone doubling is not desired, press the PRIOR/NO button.
The 16 zones will remain EOL terminated zones, requiring Normally Closed devices only.
Refer to Wiring Diagram and Installation Instructions for wiring instructions
Fire Zones in Area 1 (New Program Only)
Enter the zone number of any Fire Zones (including 2-wire, 4-wire or wireless).
Valid entries are from 01 to 64.
Directly enter each zone number, including leading zeros, and press
for any additional zone(s). Press the NEXT/YES button to proceed.
2-Wire Fire Zones in Area 1 (New Program Only)
Enter the zone number of any Fire Zone (from previous question) to be used with 2-wire smoke
° °
detectors.
Valid entries are 07 and 08. Directly enter each zone number, including leading zeros.
U
Press
to save, and repeat for any additional zone(s); press NEXT/YES to proceed.
NOTE: Only zones which have been designated as Fire Zones can be programmed as 2 Wire Fire
zones. JP3 must be set to "2-WF" position for 2-wire fire. (refer to Installation Instructions).
Local or Central Station Reporting System (New Program Only)
Press the NEXT/YES button for all zones to report; press the PRIOR/NO button for local system
Exit/Entry Zones in Area 1 (New Program Only)
Enter the zone numbers of zones to be used as Exit/Entry zones.
X X
Valid entries are from 01 to 64. Directly enter each zone number, including leading zeros.
U
Press
to save and repeat for any additional zone(s); press the NEXT/YES button to proceed.
NOTE: Exit/Entry Entry time of 30 seconds will automatically be programmed.
Interior Zones in Area 1 (New Program Only)
Enter the zone numbers to be used as Interior Zones.
X X
Valid entries are from 01 to 64. Directly enter each zone number, including leading zeros.
U
Press
to save and then repeat for any additional zone(s).
Press the NEXT/YES button to proceed.
All Interior zones will also be automatically programmed as "Exit/Entry Follower" and as "Power
Up Delay" zones.
24 Hour Zones in Area 1 (New Program Only)
Enter the zone numbers of zones to be used as 24 Hour zones.
° °
Valid entries are from 01 to 64. Directly enter each zone number, including leading zeros.
U
Press
to save and repeat for any additional zone(s); press the NEXT/YES button to proceed.
NOTE: 24 Hour Zones will automatically be programmed as audible (Burg Output).
U
to save and
U
to save. Press the NEXT/YES button to proceed.
WI1502A 9/06
to set cursor, the
R
twice to exit at any time.
C
U
to save, and then repeat
L
NAPCO Security Systems