STEP 5: RELAY EVENT CONDITION OPTIONS:
timeout type for each.
5A. Select Alarm Type and Timeout Type from Table 5A (below); enter in corresponding address location (left digit). NOTE: Select Timeout from
Step 3.
5B. Select Activation from from Table 5B (below); enter in corresponding address location (right digit).
ALARM TYPE OPTIONS
LEFT DATA
ENTRIES
blank (•)
1
4
8
9
C
NUMBER OF REL AY BOARD MOD ULES (ADDRESS 3777)
ADDRESS 3777
Number of Relay
LEFT
RIGHT
Board Modules
blank (•)
[Default = blank (•) blank (•)]
L
NAPCO Security Systems
Each relay event can be assigned an alarm type; and an activation condition; also, select a
TABLE 5A
RELAY EVENT
ALARM
TIMEOUT
TYPE
TYPE
Burglary
Minutes
Fire
Minutes
Day Zone
Minutes
Burglary
Seconds
Fire
Seconds
Day Zone
Seconds
DATA
Relay Board Module(s)
RIGHT
blank (•)
None
1
1
2
2
3
3
TABLE 5B
RELAY EVENT
ACTIVATION CONDITIONS
RIGHT DATA ENTRIES
OPTIONS
1
Alarm
2
Restore
3
Trouble
4
Trouble Restore
5
Follows Open Zone
6
Follows Shorted Zone
RELAY BOARD MODULES: Up to 3 External Relay Board
Modules (RM3008) may be programmed.
1. Select the number of relay modules from the table
shown.
2. Enter in corresponding right digit address location
shown (left digit is not used).
X
GEM-P3200 Programming Instructions
Page 51