Output terminal function selection

You can change the functions of the open collector and contact output terminals.
Parameter
Name
RUN terminal
64
function
selection
A, B, C
terminal
65
function
selection
<Setting>
Signal
Setting
Name
0
RUN Inverter running
1
SU
Up to frequency
3
OL
Overload alarm
Output frequency
4
FU
detection
Inverter operation
11
RY
ready
Output current
12
Y12
detection
Zero current
13
Y13
detection
14
FDN PID lower limit
15
FUP
PID upper limit
PID forward-reverse
16
RL
rotation output
98
LF
Minor fault output
99
ABC Alarm output
REMARKS
The same function may be set to more than one terminal.
Factory
Setting
Setting
Range
0
0, 1, 3, 4,
11 to 16,
98, 99
99
Function
Output during operation when the
inverter output frequency rises to or
above the starting frequency.
Output when the output frequency is
reached.
Output while stall prevention function
is activated.
Output when the output frequency
rises to or above the setting.
Output when the inverter is ready to
be started by switching the start
signal on.
Output when the output current rises
to or above the setting.
Output when the output current
reaches 0.
Outputs the detection signal under
PID control.
Output when a minor fault (fan failure
or communication error warning)
occurs.
Output when the inverter's protective
function is activated to stop the output
(major fault).
Setting is enabled when Pr. 30 = "1"
Operation
90
Remarks
Parameters
Referred to
Pr. 2, Pr.13
Pr. 41
Pr. 21, Pr. 22,
Pr. 23, Pr. 28
Pr. 42, Pr. 43
Pr. 48, Pr. 49
Pr. 50, Pr. 51
Pr. 88 to Pr. 94
Pr. 76, Pr. n5