Mitsubishi FR - S500 Instruction Manual page 19

Transistorized inverter
Hide thumbs Also See for FR - S500:
Table of Contents

Advertisement

Symbol
Terminal Name
Frequency
5
setting input
common
A
B
Alarm output
C
RUN
Inverter running
Open collector
SE
output common
For meter
Analog signal
output
RS-485 connector
(*3)
*1. Do not connect terminals SD and PC each other or to the earth.
For sink logic, terminal SD acts as the common terminal of contact input. For
source logic, terminal PC acts as the common terminal of contact input. (Refer
to page 25 for the way to switch between them.)
*2. Low indicates that the open collector outputting transistor is on (conducts).
High indicates that the transistor is off (does not conduct).
*3. Compatible with only the type having RS-485 communication function.
(Refer to page 41.)
*4. RL, RM, RH, RT, AU, STOP, MRS, OH, REX, JOG, RES, X14, X16, (STR)
signal selection (Refer to page 88.)
*5. RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL, LF, ABC signal selection
(Refer to page 90.)
*6. To be compatible with the European Directive (Low Voltage Directive), the
operating capacity of relay outputs (A, B, C) should be 30V 0.3A DC.
Common terminal for the frequency setting signals
(terminals 2, 4) and indicator connection (terminal AM).
Isolated from terminals SD and SE. Do not earth.
Change-over contact output indicating
that the output has been stopped by the
inverter's protective function activated.
230V 0.3A AC, 30V 0.3A DC. Alarm:
discontinuity across B-C (continuity
across A-C), normal: continuity across
B-C (discontinuity across A-C). (*6)
Switched low when the inverter output
frequency is equal to or higher than the
starting frequency (factory set to 0.5Hz,
variable). Switched high during stop or
DC injection brake operation. (*2)
Permissible load 24VDC 0.1A DC.
Common terminal for inverter running terminal RUN.
Isolated from terminals 5 and SD.
One selected from
output frequency
and motor current is
output.
The output signal is
proportional to the
magnitude of each
monitoring item.
Using the parameter unit connection cable (FR-CB201 to
205), the parameter unit (FR-PU04) is connectable.
Communication operation can be performed through
RS-485.
10
Description
Output
terminal
function
selection
(Pr. 64, Pr. 65)
changes the
terminal
functions. (*5)
Factory setting of output item:
Frequency
Permissible load current 1mA
1440 pulses/s at 60Hz
Factory setting of output item:
Frequency
Output signal 0 to 5VDC
Permissible load current 1mA