Layout And Wiring Of Main Circuit Terminals - Mitsubishi FR - S500 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR - S500:
Table of Contents

Advertisement

NOTE
To prevent a malfunction due to noise, keep the signal cables more than 10cm
(3.94inches) away from the power cables.
FR-S510W-0.1K to 0.75K-NA
NFB
Power supply
REMARKS
To ensure safety, connect the power input to the inverter via a magnetic contactor
and earth leakage circuit breaker or no-fuse breaker, and use the magnetic
contactor to switch power on-off.
The output is three-phase 200V.
1

.2.2 Layout and wiring of main circuit terminals

FR-S520-0.1K, 0.2K, 0.4K, 0.75K-NA
R
S
T
Power
supply
FR-S510W-0.1K, 0.2K, 0.4K-NA
R
S
Power
supply
CAUTION
The power supply cables must be connected to R, S, T. If they are connected to
U, V, W, the inverter will be damaged. (Phase sequence need not be matched.)
Connect the motor to U, V, W.
Turning on the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.
MC
R
S
Jumper
N
P1
P
U
V
W
IM
Motor
N
P
U
V
W
IM
Motor
U
V
W
FR-S520-1.5K, 2.2K, 3.7K-NA
FR-S540-0.4K, 0.75K, 1.5K, 2.2K, 3.7K-NA (R)
Jumper
N
P
P1
R
Power
supply
FR-S510W-0.75K-NA
N
P
R
Power
supply
5
Motor
IM
Earth
(Ground)
S
T
U
V
W
IM
Motor
S
U
V
W
IM
Motor
1