E 2 Prom Write Selection - Mitsubishi FR - S500 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR - S500:
Table of Contents

Advertisement

<Setting>
n10
Setting
Pr. 79
0
1
2
3
4
0
(Factory
setting)
7
8
0
1
2
3
1
4
7
8
n10 can be changed independently of the operation mode of the operation panel.
Setting of n10 = "1" is made valid when "0" or "2" is set in Pr. 79 "operation mode
selection".
Refer to
2
2
.14.4
E
PROM write selection
You can choose whether the parameters are stored into E
parameter setting for computer communication.
Parameter
2
E
PROM write
n12 (342)
selection
The parameter number in parentheses is the one for use of the parameter unit (FR-PU04).
* When reset is performed, the parameter value will be the value of E
Operation Mode
PU or external operation Placed in the external operation mode.
PU operation
External operation
External/PU combined
operation mode
External/PU combined
operation mode
External operation mode
External/PU combined
operation mode
Computer link operation
PU operation only
Computer link operation
External/PU combined
operation
External/PU combined
operation
External operation (PU
operation interlock)
PU or external (signal
switching)
to
(page 118)
Factory
Name
Setting
0
Mode at Power-On or at Power Restoration
after Instantaneous Power Failure
Placed in the PU operation mode.
Placed in the external operation mode.
The running frequency is given in the PU
operation mode and the start signal in the
external operation mode.
The running frequency is given in the external
operation mode and the start signal in the PU
operation mode.
MRS signal ON .....Can be switched to PU
MRS signal OFF ...Switching to PU operation
X16 signal ON .......Switched to external
X16 signal OFF .....Switched to PU operation
Disabled when PU is selected. Enabled when
external is selected.
Disabled
Enabled
Disabled
Disabled
Enabled only for external operation when the
PU interlock signal (MRS) is ON.
Enabled only for external operation (X16: ON).
Setting
Range
0: Written to RAM and E
1: Written to RAM only
0, 1
Not written to E
Setting is enabled when Pr. 30 = "1"
132
operation mode.
(Output stop during
external operation)
mode inhibited.
operation mode.
mode.
2
PROM or not at the
Remarks
2
PROM
2
PROM*
2
PROM.