Operation functions
Running status
Japanese
For meter
NA, EC
Protective/alarm functions
Ambient temperature
Ambient humidity
Storage temperature
Ambience
Altitude, vibration
*1. When undervoltage or instantaneous power failure occurs, no alarm output is
provided but the output is shut off. After power restoration, the inverter may be
run as it is. Depending on the running status (e.g. load magnitude), however,
overcurrent, regenerative overvoltage or other protection may be activated at
power restoration. (In external operation mode.)
*2. The braking torque indicated is a short-duration average torque (which varies
with motor loss) when the motor alone is decelerated from 60Hz in the shortest
time and is not a continuous regenerative torque. When the motor is
decelerated from the frequency higher than the base frequency, the average
deceleration torque will reduce.
*3. This function is valid for only the type with RS-485 communication function.
*4. Compatible with only the product having the built-in cooling fan.
*5. Activated only when "1" is set in Pr. 40 "start-time ground fault detection
selection".
*6. Activated only when external thermal relay input (OH) is selected in any of Pr. 60
to Pr. 63 (input terminal function selection).
Maximum and minimum frequency setting, frequency jump
operation, external thermal relay input selection, automatic
restart after instantaneous power failure, forward/reverse
rotation prevention, slip compensation, operation mode
selection, PID control, computer link operation (RS-485)
(*3)
1 open collector signal can be selected from
among inverter running, up-to-frequency,
frequency detection, overload warning, zero
current detection, output current detection, PID
upper limit, PID lower limit, PID forward/reverse
rotation, operation ready, minor failure and
alarm. 1 contact output (1 contact, 230V 0.3A
AC, 30V 0.3A DC) signal can be selected.
1 signal can be selected from output frequency and motor
current.
Pulse train output (1440 pulses/s, 1mA full scale)
1 signal can be selected from output frequency and motor
current.
Analog output (0 to 5VDC, 1mA full scale)
Overcurrent shut-off (during acceleration, deceleration,
constant speed), regenerative overvoltage shut-off (during
acceleration, deceleration, constant speed), overload shut-
off (electronic overcurrent protection), fin overheat, fan
failure (*4), stall prevention, start-time output side ground
fault protection (*5), external thermal relay (*6), PU
disconnection (*3), retry count excess, communication
error (*3), CPU error, undervoltage (*1)
-10ºC to +50ºC (14 F to 122 F) (non-freezing) (-10 C to
+40 C (14 F to 104 F) for totally enclosed structure feature)
90%RH maximum. (non-condensing)
-20ºC to +65ºC (-4 F to 149 F)
Indoors (without corrosive gas, flammable gas, oil mist,
dust and dirt etc.)
Maximum 1000m (3280.80feet) above sea level for standard
operation.
2
5.9m/s
or less (conforming to JIS C 0040)
166
Use
Pr. 64 to
Pr. 65 for
selection.
4