Mitsubishi FR - S500 Instruction Manual page 117

Transistorized inverter
Hide thumbs Also See for FR - S500:
Table of Contents

Advertisement

<Set point input calibration>
1. Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2-5.
2. Make calibration using the calibration parameters C2, C3. At this time, enter in C2
the frequency which should be output by the inverter at the deviation of 0% (e.g.
0Hz). (When using the FR-PU04, make calibration with Pr. 902.)
3. Apply the voltage of 100% set point (e.g. 5V) to across terminals 2-5.
4. Make calibration using Pr. 38 and calibration parameter C4. At this time, enter in
Pr. 38 the frequency which should be output by the inverter at the deviation of
100% (e.g. 60Hz). (When using the FR-PU04, make calibration with Pr. 903.)
<Detector output calibration>
1. Apply the output current of 0% detector setting (e.g. 4mA) across terminals 4-5.
2. Make calibration using the calibration parameter C6. (When using the FR-PU04,
make calibration with Pr. 904.)
3. Apply the output current of 100% detector setting (e.g. 20mA) across terminals 4-5.
4. Make calibration using the calibration parameter C7. (When using the FR-PU04,
make calibration with Pr. 905.)
Note: The frequencies set in the calibration parameter C5 and Pr. 39 should be equal
to those set in the calibration parameter C2 and Pr. 38, respectively.
The results of the above calibration are as shown below:
[Set point setting]
(%)
100
0
0
REMARKS
If the multi-speed (RH, RM, RL) signal or jog operation (jog) signal is entered,
PID control is stopped and multi-speed or jog operation is started.
When the terminal functions are changed using Pr. 60 to Pr. 65, the other
functions may be affected. Confirm the functions of the corresponding terminals
before making settings.
When PID control is selected, the minimum frequency is the frequency set in the
calibration parameter C2 and the maximum frequency is the frequency set in
Pr. 38. (The Pr. 1 "maximum frequency" and Pr. 2 "minimum frequency" settings
are also valid.)
Related parameters
X14 signal assignment
FUP, FDN and RL signal assignment
Voltage input selection (0 to ±5V, 0 to ±10V)
Operation mode selection
Making terminal calibration
[Detection value]
(%)
100
0
5
(V)
0
4
Pr. 60 to Pr. 63 (input terminal function selection) (refer to page 88)
Pr. 79 "operation mode selection" (refer to page 98)
Pr. 38, Pr. 39, C2 to C7 (calibration parameters) (refer to page 74)
Manipulated
variable (Hz)
60
20 (mA)
Pr. 64 "RUN terminal function selection", Pr. 65 "A, B,
C terminal function selection" (refer to page 90)
Pr. 73 "0-5V/0-10V selection" (refer to page 93)
108
[Manipulated variable]
0
0
100 Deviation (%)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents