" Output terminal function selection (Pr. 190 to Pr. 192)
4.2.37 Output terminal (DeviceNet input) function selection (Pr. 190
to Pr. 192)
Pr. 190 "(RUN) function selection"
Pr. 191 "(FU) function selection"
Pr. 192 "A, B, C terminal (ABC) function selection"
You can change the functions of the contact output terminals (DeviceNet input).
Inverter status is not returned. Refer to page 53 for details.
Terminal
Parameter
(DeviceNet
Number
input) Symbol
190
(RUN)
191
(FU)
192
A, B, C (ABC)
<Setting>
Refer to the following table and set the parameters:
Signal
Setting
Function
Name
0
RUN Inverter running
1
SU
Up to frequency
3
OL
Overload alarm
Output
4
FU
frequency
detection
Inverter
11
RY
operation ready
Output current
12
Y12
detection
Zero current
13
Y13
detection
Minor fault
98
LF
output
99
ABC Alarm output
Use the contact output terminals for the shaded signals.
Note: 1. The same function may be set to more than one terminal (DeviceNet output).
2. Pr. 190 to Pr. 192 do not function if the values set are other than the above.
Factory
Factory-Set Terminal
Setting
Function
0
Inverter running
Output frequency
4
detection
99
Alarm output
Operation
Output during operation when
the inverter output frequency
rises to or above the starting
frequency.
Refer to Pr. 41 "up-to-frequency
sensitivity". (Note 1)
Output while stall prevention
function is activated.
Refer to Pr. 42, Pr. 43 (output
frequency detection).
Output when the inverter is
ready to be started by switching
the start signal on.
Refer to Pr. 150 and Pr. 151
(output current detection).
Refer to Pr. 152 and Pr. 153
(zero current detection).
Output when a minor fault (fan
failure or communication error
warning) occurs.
Output when the inverter's
protective function is activated
to stop the output (major fault).
120
Get other manuals https://www.bkmanuals.com
PARAMETERS
Setting
Remarks
Range
0 to 99
DeviceNet
output
0 to 99
DeviceNet
output,
0 to 99
contact
output
terminal
DeviceNet
Related
output
Parameters
(Inverter
status)

0 Bit
Pr. 41
3 Bit
Pr. 22,
Pr. 23,
4 Bit
Pr. 66
Pr. 42,
6 Bit
Pr. 43


Pr. 150,

Pr. 151
Pr. 152,

Pr. 153
Pr. 121,

Pr. 244

7 Bit