FREQROL Inverter Driver Introduction This manual describes how to connect the Display and the External Device (target PLC). In this manual, the connection procedure is described in the sections identified below: System Configuration "1 System Configuration" (page 3) This section lists the types of External Devices and SIO that you can connect.
FREQROL Inverter Driver System Configuration The following table lists system configurations for connecting Mitsubishi Electric Corporation External Devices and the Display. • If problems such as communication interruptions due to a disconnection of the signal wire or malfunction of the Display cannot be detected on the inverter side, implement a precautionary measure by using the inverter’s communication retry function or...
Page 4
FREQROL Inverter Driver Series Inverter Link I/F SIO Type Setting Example Cable Diagram PU connector on RS-422/485 "Setting Example 9" " Cable Diagram 4" the Inverter (4 wire ) (page 26) (page 84) FR-V520L- K FR-V500L FR-V540L- K Terminal on RS-422/485 "Setting Example "...
Page 5
FREQROL Inverter Driver Series Inverter Link I/F SIO Type Setting Example Cable Diagram PU connector on RS-422/485 "Setting Example " Cable Diagram 1" the Inverter (4 wire ) 22" (page 52) (page 62) FR-B- K RS-422/485 "Setting Example " Cable Diagram 2" B,B3(A700) FR-B3-(N)(H) K (4 wire )
Page 6
FREQROL Inverter Driver Connection Configuration • 1:1 Connection External Device Display • 1:n Connection External Device External Device External Device Display Maximum number of External Devices: 16 External Device External Device External Device Maximum number of External Devices: 32 Display External Device External Device External Device GP-Pro EX Device/PLC Connection Manual...
Page 7
FREQROL Inverter Driver IPC COM Port When connecting IPC with an External Device, the COM port used depends on the series and SIO type. Please refer to the IPC manual for details. Usable port Usable Port Series RS-232C RS-422/485(4 wire) RS-422/485(2 wire) COM1 , COM2,...
Page 8
FREQROL Inverter Driver DIP Switch setting: RS-422/485 (4 wire) DIP Switch Setting Description Reserved (always OFF) SIO type: RS-422/485 Output mode of SD (TXD) data: Always output Terminal resistance (220Ω) insertion to SD (TXD): None Terminal resistance (220Ω) insertion to RD (RXD): None Short-circuit of SDA (TXA) and RDA (RXA): Not available Short-circuit of SDB (TXB) and RDB (RXB): Not available RS (RTS) Auto control mode: Disabled...
Enter an integer from 1 to 4 to define the number of Devices/PLCs to connect to the Number of Devices/PLCs display. Select the manufacturer of the External Device to connect. Select "Mitsubishi Electric Manufacturer Corporation". Select the External Device model (series) and the connection method. Select "FREQROL Inverter".
FREQROL Inverter Driver Communication Settings This section provides examples of communication settings recommended by Pro-face for the Display and the External Device. Setting Example 1 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings]...
Page 11
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 12
FREQROL Inverter Driver Setting Example 2 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 13
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 14
FREQROL Inverter Driver Setting Example 3 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 15
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 16
FREQROL Inverter Driver Setting Example 4 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 17
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 18
FREQROL Inverter Driver Setting Example 5 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 19
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 20
FREQROL Inverter Driver Setting Example 6 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 21
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 22
FREQROL Inverter Driver Setting Example 7 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 23
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 24
FREQROL Inverter Driver Setting Example 8 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 25
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 26
FREQROL Inverter Driver Setting Example 9 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 27
FREQROL Inverter Driver External Device Settings Use the MODE key, SET key, up key, and down key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Press MODE key to select the parameter setting mode. Press SET key.
Page 28
FREQROL Inverter Driver 3.10 Setting Example 10 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 29
FREQROL Inverter Driver External Device Settings Use the MODE key, SET key, up key, and down key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Press MODE key to select the parameter setting mode. Press SET key.
Page 30
FREQROL Inverter Driver 3.11 Setting Example 11 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 31
FREQROL Inverter Driver External Device Settings Use the MODE key, SET key, up key, and down key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Press MODE key to select the parameter setting mode. Press SET key.
Page 32
FREQROL Inverter Driver 3.12 Setting Example 12 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 33
FREQROL Inverter Driver External Device Settings Use the MODE key, SET key, up key, and down key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Press MODE key to select the parameter setting mode. Press SET key.
Page 34
FREQROL Inverter Driver 3.13 Setting Example 13 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 35
FREQROL Inverter Driver External Device Settings Use the MODE key, SET key, up key, and down key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Press MODE key to select the parameter setting mode. Press SET key.
Page 36
FREQROL Inverter Driver 3.14 Setting Example 14 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 37
FREQROL Inverter Driver External Device Settings Use the MODE key, SET key, up key, and down key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Press MODE key to select the parameter setting mode. Press SET key.
Page 38
FREQROL Inverter Driver 3.15 Setting Example 15 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 39
FREQROL Inverter Driver External Device Settings Use the MODE key, SET key, up key, and down key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Press MODE key to select the parameter setting mode. Press SET key.
Page 40
FREQROL Inverter Driver 3.16 Setting Example 16 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 41
FREQROL Inverter Driver External Device Settings Use the PU/EXT key in the operation panel of the CPU unit and inverter setup software by Mitsubishi Electric Corporation for External Device communication settings. Refer to your External Device manual for details. Press PU/EXT key to select the PU operation mode.
Page 42
FREQROL Inverter Driver 3.17 Setting Example 17 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 43
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 44
FREQROL Inverter Driver 3.18 Setting Example 18 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 45
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 46
FREQROL Inverter Driver 3.19 Setting Example 19 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 47
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 48
FREQROL Inverter Driver 3.20 Setting Example 20 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 49
FREQROL Inverter Driver External Device Settings Use the MODE key, SET key, up key, and down key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Press MODE key to select the parameter setting mode. Press SET key.
Page 50
FREQROL Inverter Driver 3.21 Setting Example 21 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 51
FREQROL Inverter Driver External Device Settings Use the MODE key, SET key, up key, and down key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Press MODE key to select the parameter setting mode. Press SET key.
Page 52
FREQROL Inverter Driver 3.22 Setting Example 22 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 53
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 54
FREQROL Inverter Driver 3.23 Setting Example 23 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 55
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
Page 56
FREQROL Inverter Driver 3.24 Setting Example 24 GP Pro-EX Settings Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC]. Device Setting To display the [Individual Device Settings] dialog box, from [Device-Specific Settings] in the [Device/PLC] window, select the external device and click [Settings] .
Page 57
FREQROL Inverter Driver External Device Settings Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device communication settings. Refer to your External Device manual for details. Turn ON the power supply. Press PU/EXT key to select the PU operation mode.
FREQROL Inverter Driver Setup Items Set up the Display’s communication settings in GP Pro-EX or in the Display’s offline mode. The setting of each parameter must match that of the External Device. "3 Communication Settings" (page 10) Setup Items in GP Pro-EX Communication Settings To display the setup screen, from the [Project] menu, point to [System Settings] and select [Device/PLC].
Page 59
FREQROL Inverter Driver Setup Items Setup Description Select the communication control method to prevent overflow of transmission and Flow Control reception data. Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the Timeout response from the External Device.
Page 60
FREQROL Inverter Driver Setup Items in Offline Mode • Refer to the Maintenance/Troubleshooting guide for information on how to enter offline mode or about the operation. Maintenance/Troubleshooting Guide "Offline Mode" • The number of the setup items to be displayed for 1 page in the offline mode depends on the Display in use.
Page 61
FREQROL Inverter Driver Setup Items Setup Description Select the communication control method to prevent overflow of transmission and reception Flow Control data. Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the Timeout (s) response from the External Device.
FREQROL Inverter Driver Cable Diagrams The cable diagrams shown below may be different from cable diagrams recommended by Mitsubishi Electric Corporation. Please be assured there is no operational problem in applying the cable diagrams shown in this manual. • The FG pin of the External Device body must be D-class grounded. Please refer to the manual of the External Device for more details.
Page 63
Conversion Adapter, refer to Cable Diagram 1A. Recommended cables and connectors Item Type Manufacturer 10BASE-T cable SGLPEV-T 0.5mmx4P Mitsubishi Electric Corporation RJ45 connector 5-554720-3 Tyco Electronics AMP K.K. Do not use pin number 2 or 8. External Device side Display side...
Page 64
FREQROL Inverter Driver External Device side Display side RJ45 connector Terminal Block Signal name Signal name CA4-ADPONL-01 Display CA3-ADPTRM-01 User-created cable Display side D-Sub 9pin (plug) External Device side Signal name RJ45 connector Signal name TERMRX CA4-ADPONL-01 Display TERMTX Shell User-created cable GP-Pro EX Device/PLC Connection Manual...
Page 65
FREQROL Inverter Driver Display side External Device side Terminal block RJ45 connector Signal name Signal name Display External Device side Display side RJ45 connector Terminal Block Signal name Signal name Display PFXZCBADTM1 User-created cable GP-Pro EX Device/PLC Connection Manual...
Page 66
FREQROL Inverter Driver Cable Diagram 2 Display Cable Notes (Connection Port) COM port conversion adapter by Pro-face CA3-ADPCOM-01 GP3000 (COM1) AGP-3302B (COM2) Terminal block conversion adapter by Pro-face GP-4*01TM (COM1) Cable length: CA3-ADPTRM-01 (COM2) 500m or less LT3000 (COM1) User-created cable User-created cable Online adapter by Pro-face CA4-ADPONL-01...
Page 67
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block CA3-ADPCOM-01 Shield Display TERM Signal name SDA1 (TXD1+) SDB1 (TXD1-) RDA1 (RXD1+) CA3-ADPTRM-01 RDB1 (RXD1-) SG (GND) User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 68
FREQROL Inverter Driver • 1:1 Connection Display side External Device side D-Sub 9pin (socket) Terminal Block Termination Signal name resistance Shield Signal name 100Ω (1/2W) SDA1 (TXD1+) SDB1 (TXD1-) Display RDA1 (RXD1+) RDB1 (RXD1-) SG (GND) Shell • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 69
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block CA4-ADPONL-01 Shield Display TERM Signal name SDA1 (TXD1+) SDB1 (TXD1-) RDA1 (RXD1+) CA3-ADPTRM-01 RDB1 (RXD1-) SG (GND) User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 70
FREQROL Inverter Driver • 1:1 Connection Display side D-Sub 9pin (plug) External Device side Signal name Terminal Block Shield TERMRX Signal name CA4-ADPONL-01 SDA1 (TXD1+) Display SDB1 (TXD1-) RDA1 (RXD1+) RDB1 (RXD1-) SG (GND) TERMTX Shell User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 71
FREQROL Inverter Driver • 1:1 Connection Display side External Device side Terminal block Terminal Block Signal name Termination Shield Signal name resistance*1 SDA1 (TXD1+) SDB1 (TXD1-) Display RDA1 (RXD1+) RDB1 (RXD1-) SG (GND) • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 72
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block Shield Display TERM Signal name SDA1 (TXD1+) SDB1 (TXD1-) RDA1 (RXD1+) PFXZCBADTM1 RDB1 (RXD1-) SG (GND) User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 73
FREQROL Inverter Driver Cable Diagram 3 Display Cable Notes (Connection Port) COM port conversion adapter by Pro-face CA3-ADPCOM-01 GP3000 (COM1) AGP-3302B (COM2) Terminal block conversion adapter by Pro-face Cable length: GP-4*01TM (COM1) CA3-ADPTRM-01 500m or less (COM2) LT3000 (COM1) User-created cable User-created cable Online adapter by Pro-face CA4-ADPONL-01...
FREQROL Inverter Driver Only the COM port which can communicate by RS-422/485 (2 wire) can be used. " IPC COM Port" (page 7) Except GP-4203T All GP4000 models except GP-4100 Series, GP-4*01TM, GP-4201T and GP-4*03T When using a Terminal Block Conversion Adapter (CA3-ADPTRM-01) instead of the RS-422 Terminal Block Conversion Adapter, refer to Cable Diagram 3A.
Page 75
FREQROL Inverter Driver • 1:1 Connection Display side External Device side D-Sub 9pin (socket) Terminal Block Termination Signal name Shield resistance Signal name 100Ω (1/2W) SDA1 (TXD1+) SDB1 (TXD1-) RDA1 (RXD1+) Display RDB1 (RXD1-) SG (GND) Shell • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 76
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block CA4-ADPONL-01 Shield Display TERM Signal name SDA1 (TXD1+) SDB1 (TXD1-) RDA1 (RXD1+) CA3-ADPTRM-01 RDB1 (RXD1-) SG (GND) User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 77
FREQROL Inverter Driver • 1:1 Connection Display side D-Sub 9pin (plug) External Device side Terminal Block Signal name Shield TERMRX Signal name CA4-ADPONL-01 SDA1 (TXD1+) Display SDB1 (TXD1-) RDA1 (RXD1+) RDB1 (RXD1-) SG (GND) TERMTX Shell User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 78
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block CA3-ADPCOM-01 Shield Display TERM Signal name SDA1 (TXD1+) SDB1 (TXD1-) RDA1 (RXD1+) CA3-ADPTRM-01 RDB1 (RXD1-) SG (GND) User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 79
FREQROL Inverter Driver • 1:1 Connection Display side External Device side D-Sub 9pin (socket) Terminal Block Termination Signal name resistance Shield Signal name 100Ω (1/2W) DATA+ SDA1 (TXD1+) DATA- SDB1 (TXD1-) RDA1 (RXD1+) Display RDB1 (RXD1-) GND(SG) SG (GND) Shell •...
Page 80
FREQROL Inverter Driver • 1:1 Connection Display side External Device side Terminal block Terminal Block Signal name Shield Signal name Termination resistance*1 SDA1 (TXD1+) SDB1 (TXD1-) RDA1 (RXD1+) Display RDB1 (RXD1-) SG (GND) • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 81
FREQROL Inverter Driver • 1:1 Connection Display side External Device side D-Sub 9pin (plug) Terminal Block Termination Signal name Shield resistance Signal name 100Ω (1/2W) LINE(+) SDA1 (TXD1+) LINE(-) SDB1 (TXD1-) RDA1 (RXD1+) Display RDB1 (RXD1-) SG (GND) GND(SG) RS(RTS) Shell •...
Page 82
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block Shield Display TERM Signal name SDA1 (TXD1+) SDB1 (TXD1-) RDA1 (RXD1+) PFXZCBADTM1 RDB1 (RXD1-) SG (GND) User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 83
FREQROL Inverter Driver • 1:1 Connection External Device side Terminal Block Signal name Display SDA1 (TXD1+) SDB1 (TXD1-) RDA1 (RXD1+) RDB1 (RXD1-) SG (GND) • Please set the terminating resistor switch of the External Device to the "100Ω" position. • 1:n Connection External Device side External Device side...
When using a Terminal Block Conversion Adapter (CA3-ADPTRM-01) instead of the RS-422 Terminal Block Conversion Adapter, refer to Cable Diagram 4A. Recommended cables and connectors Item Type Manufacturer Cable FR-CB20 Mitsubishi Electric Corporation 10BASE-T cable SGLPEV-T0.5mmx4P Mitsubishi Electric Corporation RJ45 connector 5-554720-3 Tyco Electronics AMP K.K. BMJ-8 RS-485 distributor HACHIKO ELECTRIC CO.,LTD...
Page 85
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block Distributor side Signal name RJ45 connector CA3-ADPCOM-01 Signal Display TERM name External Device side Distributor side RJ45 connector RJ45 connector Signal Signal Distributor name name CA3-ADPTRM-01 (BMJ-8P) Signal name Termination resistance FR-CB20 cable...
Page 86
FREQROL Inverter Driver • 1:n Connection Display side Terminal Block Distributor side Signal name RJ45 connector CA3-ADPCOM-01 Signal Display TERM name External Device side Distributor side RJ45 connector RJ45 connector Signal Signal Distributor name name CA3-ADPTRM-01 (BMJ-8) Distributor side RJ45 connector Signal name FR-CB20...
Page 87
FREQROL Inverter Driver • 1:1 Connection Display side Distributor side D-Sub 9pin (socket) RJ45 connector Termination Signal resistance Signal name name 100Ω (1/4W) Distributor side Distributor side RJ45 connector RJ45 connector Distributor Signal Signal Display (BMJ-8P) name name Signal name Termination resistance FR-CB20...
Page 88
FREQROL Inverter Driver • 1:n Connection Display side Distributor side D-Sub 9pin (socket) RJ45 connector Termination Signal resistance Signal name name 100Ω (1/4W) Distributor side Distributor side RJ45 connector RJ45 connector Distributor Signal Signal Display (BMJ-8) name name Distributor side RJ45 connector Signal name...
Page 89
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block Distributor side Signal name RJ45 connector CA4-ADPONL -01 Signal Display TERM name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8P) name name CA3-ADPTRM-01 Signal name Termination resistance FR-CB20...
Page 90
FREQROL Inverter Driver • 1:n Connection Display side Terminal Block Distributor side Signal name RJ45 connector CA4-ADPONL -01 Signal Display TERM name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8) CA3-ADPTRM-01 name name Distributor side RJ45 connector Signal name...
Page 91
FREQROL Inverter Driver • 1:1 Connection Display side D-Sub 9pin (plug) Distributor side Signal name RJ45 connector CA4-ADPONL -01 Signal Display TERMRX name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8P) name name TERMTX Signal Shell name Termination...
Page 92
FREQROL Inverter Driver • 1:n Connection Display side D-Sub 9pin (plug) Distributor side Signal name RJ45 connector CA4-ADPONL -01 Signal Display TERMRX name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8) name name TERMTX Distributor side Shell RJ45 connector Signal...
Page 93
FREQROL Inverter Driver • 1:1 Connection Display side Distributor side Terminal block RJ45 connector Signal Termination Signal name name resistance*1 Distributor side Distributor side RJ45 connector RJ45 connector Distributor Signal Signal Display (BMJ-8P) name name Signal name Termination resistance FR-CB20 cable 100Ω...
Page 94
FREQROL Inverter Driver • 1:n Connection Display side Distributor side Terminal block RJ45 connector Signal Termination Signal name name resistance*1 Distributor side Distributor side RJ45 connector RJ45 connector Distributor Signal Signal Display (BMJ-8) name name Distributor side RJ45 connector Signal name FR-CB20 cable...
Page 95
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block Distributor side Signal name RJ45 connector Signal Display TERM name External Device side Distributor side RJ45 connector RJ45 connector Signal Signal Distributor name name PFXZCBADTM1 (BMJ-8P) Signal name Termination resistance FR-CB20 cable 100Ω...
Page 96
FREQROL Inverter Driver • 1:n Connection Display side Terminal Block Distributor side Signal name RJ45 connector Signal Display TERM name External Device side Distributor side RJ45 connector RJ45 connector Signal Signal Distributor name name PFXZCBADTM1 (BMJ-8) Distributor side RJ45 connector Signal name FR-CB20...
When using a Terminal Block Conversion Adapter (CA3-ADPTRM-01) instead of the RS-422 Terminal Block Conversion Adapter, refer to Cable Diagram 5A. Recommended cables and connectors Item Type Manufacturer 10BASE-T cable SGLPEV-T0.5mmx4P Mitsubishi Electric Corporation RJ45 connector 5-554720-3 Tyco Electronics AMP K.K. BMJ-8 RS-485 distributor HACHIKO ELECTRIC CO.,LTD BMJ-8P Do not use pin number 2 or 8.
Page 99
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block Distributor side Signal name RJ45 connector CA3-ADPCOM-01 Signal Display TERM name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8P) name name CA3-ADPTRM-01 Signal name Termination resistance 100Ω...
Page 100
FREQROL Inverter Driver • 1:n Connection Display side Terminal Block Distributor side Signal name RJ45 connector CA3-ADPCOM-01 Signal Display TERM name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8) name name CA3-ADPTRM-01 Distributor side RJ45 connector Signal name Distributor side...
Page 101
FREQROL Inverter Driver • 1:1 Connection Display side Distributor side D-Sub 9pin (socket) RJ45 connector Termination Signal resistance Signal name name 100Ω (1/4W) Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal Display (BMJ-8P) name name Signal name Termination resistance...
Page 102
FREQROL Inverter Driver • 1:n Connection Display side Distributor side D-Sub 9pin (socket) RJ45 connector Termination Signal resistance Signal name name 100Ω (1/4W) Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal Display (BMJ-8) name name Distributor side RJ45 connector Signal name...
Page 103
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block Distributor side Signal name RJ45 connector CA4-ADPONL-01 Signal Display TERM name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8P) CA3-ADPTRM-01 name name Signal name Termination resistance 100Ω...
Page 104
FREQROL Inverter Driver • 1:n Connection Display side Terminal Block Distributor side Signal name RJ45 connector CA4-ADPONL-01 Signal Display TERM name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8) CA3-ADPTRM-01 name name Distributor side RJ45 connector Signal name Distributor side...
Page 105
FREQROL Inverter Driver • 1:1 Connection Display side D-Sub 9pin (plug) Distributor side Signal name RJ45 connector CA4-ADPONL-01 Signal Display TERMRX name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8P) name name TERMTX Signal Shell name Termination resistance...
Page 106
FREQROL Inverter Driver • 1:n Connection Display side D-Sub 9pin (plug) Distributor side Signal name RJ45 connector CA4-ADPONL-01 Signal Display TERMRX name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8) name name TERMTX Distributor side Shell RJ45 connector Signal...
Page 107
FREQROL Inverter Driver • 1:1 Connection Distributor side RJ45 connector Display side Signal Terminal Block name Signal name Distributor side External Device side CA3-ADPCOM-01 Display TERM RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8P) name name CA3-ADPTRM-01 Signal name Termination resistance 100Ω...
Page 108
FREQROL Inverter Driver • 1:n Connection Distributor side RJ45 connector Display side Signal Terminal Block name Signal name Distributor side External Device side CA3-ADPCOM-01 Display TERM RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8) name name CA3-ADPTRM-01 Distributor side RJ45 connector Signal name Distributor side...
Page 109
FREQROL Inverter Driver • 1:1 Connection Distributor side RJ45 connector Signal name Display side D-Sub 9pin (socket) Termination Distributor side External Device side resistance Signal name RJ45 connector RJ45 connector Distributor 100Ω (1/4W) Signal Signal DATA+ (BMJ-8P) name name DATA- Display Signal GND(SG)
Page 110
FREQROL Inverter Driver • 1:n Connection Distributor side RJ45 connector Signal name Display side D-Sub 9pin (socket) Termination Distributor side External Device side resistance Signal name RJ45 connector RJ45 connector Distributor 100Ω (1/4W) Signal Signal DATA+ (BMJ-8) name name DATA- Display Distributor side GND(SG)
Page 111
FREQROL Inverter Driver • 1:1 Connection Display side Distributor side Terminal block RJ45 connector Signal Termination Signal name name resistance*1 Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal Display (BMJ-8P) name name Signal name Termination resistance 100Ω...
Page 112
FREQROL Inverter Driver • 1:n Connection Display side Distributor side Terminal block RJ45 connector Signal Signal name Termination name resistance*1 Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal Display (BMJ-8) name name Distributor side RJ45 connector Signal name Distributor side...
Page 113
FREQROL Inverter Driver • 1:1 Connection Distributor side RJ45 connector Signal Display side name D-Sub 9pin (plug) Termination Distributor side External Device side resistance Signal name RJ45 connector RJ45 connector Distributor 100Ω (1/4W) Signal Signal LINE(+) (BMJ-8P) name name LINE(-) Display Signal GND(SG)
Page 114
FREQROL Inverter Driver • 1:n Connection Distributor side RJ45 connector Signal name Display side D-Sub 9pin (plug) Termination Distributor side External Device side resistance Signal name RJ45 connector RJ45 connector Distributor 100Ω (1/4W) Signal Signal LINE(+) (BMJ-8) name name LINE(-) Display Distributor side RJ45 connector...
Page 115
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block Distributor side Signal name RJ45 connector Signal Display TERM name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8P) name name PFXZCBADTM1 Signal name Termination resistance 100Ω...
Page 116
FREQROL Inverter Driver • 1:n Connection Display side Terminal Block Distributor side Signal name RJ45 connector Signal Display TERM name Distributor side External Device side RJ45 connector RJ45 connector Distributor Signal Signal (BMJ-8) name name PFXZCBADTM1 Distributor side RJ45 connector Signal name Distributor side...
Page 117
FREQROL Inverter Driver • 1:1 Connection Distributor side RJ45 connector Signal name Distributor side External Device side RJ45 connector RJ45 connector Display Distributor Signal Signal (BMJ-8P) name name Signal name Termination resistance 100Ω (1/4W) Distributor side RJ45 connector User-created Cable GP-Pro EX Device/PLC Connection Manual...
Page 118
FREQROL Inverter Driver • 1:n Connection Distributor side RJ45 connector Signal name Distributor side External Device side RJ45 connector RJ45 connector Distributor Display Signal Signal (BMJ-8) name name Distributor side RJ45 connector Signal name Distributor side RJ45 connector Signal name Distributor side External Device side RJ45 connector...
FREQROL Inverter Driver Only the COM port which can communicate by RS-422/485 (2 wire) can be used. " IPC COM Port" (page 7) Except GP-4203T All GP4000 models except GP-4100 Series, GP-4*01TM, GP-4201T and GP-4*03T When using a Terminal Block Conversion Adapter (CA3-ADPTRM-01) instead of the RS-422 Terminal Block Conversion Adapter, refer to Cable Diagram 6A.
Page 121
FREQROL Inverter Driver • 1:1 Connection Display side D-Sub 9pin (socket) Termination resistance Shield Signal name External Device side 100Ω (1/2W) Terminal Block Termination Signal name resistance 100Ω (1/2W) Display Shell • 1:n Connection Display side D-Sub 9pin (socket) Termination resistance Signal name Shield...
Page 122
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block Signal name Shield CA4-ADPONL-01 Display TERM External Device side Terminal Block Termination Signal name resistance 100Ω (1/2W) CA3-ADPTRM-01 User-created cable • 1:n Connection Display side Terminal Block Signal name Shield CA4-ADPONL-01 Display TERM...
Page 123
FREQROL Inverter Driver • 1:1 Connection Display side D-Sub 9pin (plug) Signal name CA4-ADPONL-01 Shield Display TERMRX External Device side Terminal Block Termination Signal name resistance 100Ω (1/2W) TERMTX Shell User-created cable • 1:n Connection Display side D-Sub 9pin (plug) Signal name CA4-ADPONL-01 Shield...
Page 124
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Terminal Block Signal name Termination Shield CA3-ADPCOM-01 Signal name resistance Display TERM 100Ω (1/2W) CA3-ADPTRM-01 User-created cable • 1:n Connection Display side Terminal Block External Device side External Device side Terminal Block Terminal Block...
Page 125
FREQROL Inverter Driver • 1:1 Connection External Device side Display side Terminal Block D-Sub 9pin (socket) Termination Termination Shield resistance Signal name resistance Signal name 100Ω (1/2W) 100Ω (1/2W) DATA+ DATA- Display GND(SG) Shell • 1:n Connection External Device side External Device side Display side Terminal Block...
Page 126
FREQROL Inverter Driver • 1:1 Connection Display side Terminal block Termination Shield Signal name External Device side resistance*1 Terminal Block Termination Signal name resistance 100Ω (1/2W) Display • 1:n Connection Display side Terminal block Termination Shield Signal name External Device side External Device side resistance*1 Terminal Block...
Page 127
FREQROL Inverter Driver • 1:1 Connection External Device side Display side Terminal Block D-Sub 9pin (plug) Termination Termination Shield resistance Signal name resistance Signal name 100Ω (1/2W) 100Ω (1/2W) LINE(+) LINE(-) Display GND(SG) RS(RTS) Shell • 1:n Connection External Device side External Device side Display side Terminal Block...
Page 128
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block Signal name Shield Display TERM External Device side Terminal Block Termination Signal name resistance 100Ω (1/2W) PFXZCBADTM1 User-created cable • 1:n Connection Display side Terminal Block Signal name Shield Display TERM External Device side External Device side...
Page 129
FREQROL Inverter Driver • 1:1 Connection External Device side Terminal Block Termination Signal name resistance Display 100Ω (1/2W) • 1:n Connection External Device side External Device side Termination Terminal Block Terminal Block resistance Termination 220Ω(1/4W) Shield Signal name resistance Signal name Display 220Ω(1/4W) User-created Cable...
FREQROL Inverter Driver Cable Diagram 7 Display Cable Notes (Connection Port) COM port conversion adapter by Pro-face CA3-ADPCOM-01 GP3000 (COM1) AGP-3302B (COM2) Terminal block conversion adapter by Pro-face GP-4*01TM (COM1) Cable length: CA3-ADPTRM-01 (COM2) 500m or less LT3000 (COM1) User-created cable User-created cable Online adapter by Pro-face CA4-ADPONL-01...
Page 131
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block CA3-ADPCOM-01 Shield Display TERM Signal name CA3-ADPTRM-01 User-created cable • 1:n Connection Display side Terminal Block External Device side External Device side Signal name Terminal Block Terminal Block CA3-ADPCOM-01...
Page 132
FREQROL Inverter Driver • 1:1 Connection External Device side Display side D-Sub 9pin (socket) Terminal Block Termination Shield resistance Signal name Signal name 100Ω (1/2W) Display Shell • 1:n Connection External Device side Display side External Device side D-Sub 9pin (socket) Terminal Block Terminal Block Termination...
Page 133
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block CA4-ADPONL-01 Shield Display TERM Signal name CA3-ADPTRM-01 User-created cable • 1:n Connection Display side Terminal Block External Device side External Device side Signal name Terminal Block Terminal Block CA4-ADPONL-01...
Page 134
FREQROL Inverter Driver • 1:1 Connection Display side D-Sub 9pin (plug) External Device side Signal name Terminal Block CA4-ADPONL-01 Shield Display TERMRX Signal name TERMTX Shell User-created cable • 1:n Connection Display side D-Sub 9pin (plug) External Device side External Device side Terminal Block Signal name Terminal Block...
Page 135
FREQROL Inverter Driver • 1:1 Connection Display side External Device side Terminal block Terminal Block Shield Signal name Signal name Termination resistance*1 Display • 1:n Connection Display side External Device side External Device side Terminal block Terminal Block Terminal Block Shield Shield Signal name...
Page 136
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block Shield Display Signal name TERM PFXZCBADTM1 User-created cable • 1:n Connection Display side Terminal Block External Device side External Device side Signal name Terminal Block Terminal Block Shield...
FREQROL Inverter Driver Cable Diagram 8 Display Cable Notes (Connection Port) COM port conversion adapter by Pro-face CA3-ADPCOM-01 GP3000 (COM1) AGP-3302B (COM2) Terminal block conversion adapter by Pro-face GP-4*01TM (COM1) Cable length: CA3-ADPTRM-01 (COM2) 500m or less LT3000 (COM1) User-created cable User-created cable Online adapter by Pro-face CA4-ADPONL-01...
Page 138
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block CA3-ADPCOM-01 Shield Display Signal name TERM CA3-ADPTRM-01 User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 139
FREQROL Inverter Driver • 1:1 Connection Display side External Device side D-Sub 9pin (socket) Terminal Block Termination Signal name resistance Shield Signal name 100Ω (1/2W) Display Shell • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 140
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block CA4-ADPONL-01 Shield Display Signal name TERM CA3-ADPTRM-01 User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 141
FREQROL Inverter Driver • 1:1 Connection Display side D-Sub 9pin (plug) External Device side Terminal Block Signal name Shield TERMRX Signal name CA4-ADPONL-01 Display TERMTX Shell User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 142
FREQROL Inverter Driver • 1:1 Connection Display side External Device side Terminal block Terminal Block Signal name Termination Shield Signal name resistance*1 Display • Please set the terminating resistor switch of the External Device to the "100Ω" position. • 1:n Connection Display side External Device side External Device side...
Page 143
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block Shield Display TERM Signal name PFXZCBADTM1 User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
FREQROL Inverter Driver Only the COM port which can communicate by RS-422/485 (2 wire) can be used. " IPC COM Port" (page 7) Except GP-4203T All GP4000 models except GP-4100 Series, GP-4*01TM, GP-4201T and GP-4*03T When using a Terminal Block Conversion Adapter (CA3-ADPTRM-01) instead of the RS-422 Terminal Block Conversion Adapter, refer to Cable Diagram 9A.
Page 146
FREQROL Inverter Driver • 1:1 Connection Display side External Device side D-Sub 9pin (socket) Terminal Block Termination Signal name Shield resistance Signal name 100Ω (1/2W) Display Shell • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 147
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block CA4-ADPONL-01 Shield Display Signal name TERM CA3-ADPTRM-01 User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 148
FREQROL Inverter Driver • 1:1 Connection Display side D-Sub 9pin (plug) External Device side Terminal Block Signal name Shield TERMRX Signal name CA4-ADPONL-01 Display TERMTX Shell User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 149
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block CA3-ADPCOM-01 Shield Display TERM Signal name CA3-ADPTRM-01 User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 150
FREQROL Inverter Driver • 1:1 Connection Display side External Device side D-Sub 9pin (socket) Terminal Block Termination Signal name Shield resistance Signal name 100Ω (1/2W) DATA+ DATA- Display GND(SG) Shell • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 151
FREQROL Inverter Driver • 1:1 Connection Display side External Device side Terminal block Terminal Block Signal name Shield Signal name Termination resistance*1 Display • Please set the terminating resistor switch of the External Device to the "100Ω" position. • 1:n Connection Display side External Device side External Device side...
Page 152
FREQROL Inverter Driver • 1:1 Connection Display side External Device side D-Sub 9pin (plug) Terminal Block Termination Signal name Shield resistance Signal name 100Ω (1/2W) LINE(+) LINE(-) Display GND(SG) RS(RTS) Shell • The 5V output (Pin #6) on the Display is the power for the Siemens AG’s PROFIBUS connector.
Page 153
FREQROL Inverter Driver • 1:1 Connection Display side Terminal Block External Device side Signal name Terminal Block Shield Display Signal name TERM PFXZCBADTM1 User-created cable • Please set the terminating resistor switch of the External Device to the "100Ω" position. •...
Page 154
FREQROL Inverter Driver • 1:1 Connection External Device side Terminal Block Signal name Display • Please set the terminating resistor switch of the External Device to the "100Ω" position. • 1:n Connection External Device side External Device side Terminal Block Terminal Block Shield Signal name...
FREQROL Inverter Driver Supported Devices The following table shows the range of supported device addresses. Please note that the actually supported range of the devices varies depending on the External Device to be used. Please check the actual range in the manual of your External Device.
Page 156
FREQROL Inverter Driver This address can be specified as system data area. Device Bit Address Word Address 32bits Notes 000.00 - 991.15 000 - 991 *2 *3 Parameter 000.00 - 993.15 000 - 993 *3 *5 Parameter P037.00 - P037.31 P037 *3 *7 *8 Setting Items and Set Data...
Page 157
FREQROL Inverter Driver Setting Items List FR-E700 series, FR-E500 series, FR-S500 series, FR-F500J series Word FR-E700 series FR-E500 series FR-S500 series FR-F500J series Address Operation mode Operation mode Operation mode Operation mode S01/ Output frequency/speed Output frequency[speed] Output frequency[speed] Output frequency[speed] SL01 Output current Output current...
Page 158
FREQROL Inverter Driver Word FR-E700 series FR-E500 series FR-S500 series FR-F500J series Address Inverter thermal load factor Alarm definition Alarm definition Alarm definition Alarm definition (Latest Nos. 1&2) (Latest Nos. 1&2) (Latest Nos. 1&2) (Latest Nos. 1&2) Alarm definition Alarm definition Alarm definition Alarm definition (Latest Nos.
Page 159
FREQROL Inverter Driver FR-A700/FR-A701 series, FR-F700 series, FR-B,B3(A700) series, FR-B,B3(A500) series Word FR-A700/FR-A701 series FR-F700 series FR-B,B3(A700) series FR-B,B3(A500) series Address Operation mode Operation mode Operation mode Operation mode Output frequency/speed Output frequency/speed Output frequency/speed Output frequency[speed] Output current Output current...
Page 160
FREQROL Inverter Driver Word FR-A700/FR-A701 series FR-F700 series FR-B,B3(A700) series FR-B,B3(A500) series Address Alarm definition Alarm definition Alarm definition Alarm definition (Latest Nos. 5&6) (Latest Nos. 5&6) (Latest Nos. 5&6) (Latest Nos. 5&6) Alarm definition Alarm definition Alarm definition Alarm definition (Latest Nos.
Page 161
FREQROL Inverter Driver FR-A500/FR-A500L series, FR-F500/FR-F500L series, FR-C500 series Word FR-A500/FR-A500L series FR-F500/FR-F500L series FR-C500 series Address Operation mode Operation mode Operation mode Output frequency[speed] Output frequency[speed] Output frequency[speed] Output current Output current Output current Output voltage Output voltage Special monitor Special monitor Special monitor selection Special monitor selection...
Page 162
FREQROL Inverter Driver Word FR-A500/FR-A500L series FR-F500/FR-F500L series FR-C500 series Address Alarm definition Alarm definition (Latest Nos. 5&6) (Latest Nos. 5&6) Alarm definition Alarm definition (Latest Nos. 7&8) (Latest Nos. 7&8) Run command Run command Run command Inverter status monitor Inverter status monitor Inverter status monitor Set frequency read (RAM)
Page 163
FREQROL Inverter Driver FR-V500/FR-V500L series Word FR-V500/FR-V500L series Address SL00 Operation mode SL01 Speed SL02 Output current SL03 Output voltage SL04 Special monitor Special monitor selection SL05 SL06 Output frequency SL07 Output current SL08 Output voltage SL09 Speed setting SL10 Running speed SL11 Motor torque...
Page 164
FREQROL Inverter Driver Word FR-V500/FR-V500L series Address Alarm definition SL45 (Latest Nos. 5&6) Alarm definition SL46 (Latest Nos. 7&8) SL47 SL48 Run command SL49 SL50 Inverter status monitor SL51 Set speed read (RAM) SL52 Set speed read (EEPROM) SL53 Set speed write (RAM) SL54 Set speed write (EEPROM) SL55...
FREQROL Inverter Driver Device Code and Address Code Use device code and address code when you set "Device Type & Address" for the address type of the data display or other devices. Device Device Name Device Code (HEX) Address Code Parameter 0080 Word Address...
FREQROL Inverter Driver Error Messages Error messages are displayed on the Display screen as follows: "No. : Device Name: Error Message (Error Occurrence Area)". Each description is shown below. Item Description Error number Name of the External Device where an error has occurred. Device/PLC name is the title of Device Name the External Device set with GP Pro-EX.
Page 167
FREQROL Inverter Driver Error No. Error Message Description Displayed when the incorrect device is used. (Node Name): Please change to use When the External Device data length is 4- RHxx130 (Device Address) to read the Setting byte and 6-byte, use the S device and the Items/data.