2
.3.19

Start-time ground fault detection selection

You can choose whether to make ground fault detection valid or invalid at a start.
Ground fault detection is executed only right after the start signal is input to the
inverter.
Parameter
Name
Start-time ground
40
fault detection
selection
CAUTION
1. If a ground fault is detected with "1" set in Pr. 40, alarm output "
and the output is shut off.
2. If the motor capacity is less than 0.1kW, ground fault protection may not be
provided.
REMARK
When a ground fault is detected with "1" set in Pr. 40, an approximate 20ms delay
occurs at every start.
2

.4 Output Terminal Function Parameters

2
.4.1

Up-to-frequency sensitivity

The ON range of the up-to-
frequency signal (SU) output
when the output frequency
reaches the running frequency
can be adjusted between 0 and
±100% of the running frequency.
This parameter can be used to
ensure that the running
frequency has been reached to
provide the operation start signal
etc. for related equipment.
Parameter
Name
Up-to-frequency
41
sensitivity
REMARKS
Using Pr. 64 or Pr. 65 to change terminal assignment may affect the other functions.
Make setting after confirming the function of each terminal. (Refer to page 90.)
Related parameters
Assignment of SU signal to terminal
Factory
Setting
Setting
Range
<EC version>
0
0, 1
<1>
Output signal
(SU)
Start signal
Factory
Setting
10%
0 to 100%
Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C
terminal function selection" (refer to page 90)
78
Remarks
0: Ground fault detection for
protection is not executed.
1: Ground fault detection for
protection is executed.
Running
frequency
OFF
ON
ON
Setting
Range
Setting is enabled when Pr. 30 =
"1".
Setting is
enabled when
Pr. 30 = "1".
" is detected
Adjustable
range
Pr.41
Time
OFF
OFF
Remarks

Hide quick links: