Parameter Name:
Auto Changeover - Temp Dead-band
Max Heat Set point
Min Cool Set point
Heat Cool Stages Lock In
Balance Point Control
Humiditrol Comfort Adjust
Humidification Control Mode
Max Humidification Setpoint
Auto Changeover - Humidif. Dead-band
Dew Point Adjustment
Humiditrol and Aux Dehum Min Run Time
HP Heating Lockout Time (enabled in zoning system) - When heat pump cannot
satisfy demand in a reason time, the control switches to gas heating and lockout
the heat pump for 120 minutes by default.
Heat Cool Stages Locked In
*1st Stage Differential
*2nd Stage Differential
*3nd Stage Differential
Stage Delay Timers
*2nd Stage Delay
*3rd Stage Delay
Electric Heat Stage During Defrost (Used to adjust the number of electric heat­
ing elements that will be energized when the heat pump is in defrost mode.)
Min De-humidification Setpoint
Outdoor Temperature Reading Calibration
Zoning Gas heating DAT Cool down Target
Zoning Anticipated Discharge Air Temperature Adjustment
Zoning Target Supply Air Temp for Cooling
Zoning Target Supply Air Temp for Gas/Electric Heating
Zoning Target Supply Air Temp for HP Heating
Zoning Supply Air Temp Limit for Cooling
Zoning Supply Air Temp Limit for Gas/Electric Heating
*Number of stages shown in thermostat is dependent on equipment that is installed. Electric heat will bring on 2 elements at a time if available.
Lock in 2nd stage HP by Outdoor Temp
HP Heating Lockout Time
Zoning Minimum Zone Run Time
Zone 1 First Stage Differential
Zone 2 First Stage Differential
Zone 3 First Stage Differential
Zone 4 First Stage Differential
Zone 1 Continuous Blower CFM
Zone 2 Continuous Blower CFM
Zone 3 Continuous Blower CFM
Zone 4 Continuous Blower CFM
Zone 1 Cooling CFM
Zone 2 Cooling CFM
Zone 3 Cooling CFM
Zone 4 Cooling CFM
Zone 1 Heating CFM
Zone 2 Heating CFM
Zone 3 Heating CFM
Zone 4 Heating CFM
®
iComfort Wi-Fi
Default
5ºF
90ºF
60ºF
60ºF
Disabled
Maximum
Maximum, Minimum and Midpoint
Overcooling
Display Only, Precision, Precision Dew Point
Basic
Control, Basic, Basic Dew Point Control
45ºF
5ºF
0ºF
15 minutes
120 minutes
Disabled
1.0ºF
1.0ºF
1.0ºF
Enabled
20 Minutes
20 Minutes
2
40
0ºF
100ºF
60 Seconds
50ºF
100ºF
90ºF
40ºF
140ºF
Off, 40ºF (4ºC), 45ºF (7ºC), 50ºF (10ºC), 55ºF
Off
120 Minutes
120 Seconds
1.0ºF
1.0ºF
1.0ºF
1.0ºF
To be determine by equipment capacity.
7-Day Programmable Communicating Thermostat
Page 9
Parameter Value Setting
3 to 9ºF
40 to 90ºF
60 to 99ºF
60 to 99ºF
Disabled or Enabled
Overcooling
15 to 45ºF
5 to 10ºF
-15ºF to 15ºF
5 to 30 minutes
60 to 240 minutes
Enabled, Disabled
0.5 to 3ºF
0.5 to 8ºF
0.5 to 8ºF
Enabled, Disabled
5 to 120 Minutes
5 to 120 Minutes
0 to 5
50 to 55 RH%
-10 to 10ºF
80 to 110ºF
0 to 120 seconds
50 to 60ºF
100 to 130ºF
85 to 110ºF
35 to 45ºF
140 to 160ºF
(13ºC)
Range is 60 to 240 minutes.
Range is 90 to 600 seconds
0.5 to 3.0ºF
0.5 to 3.0ºF
0.5 to 3.0ºF
0.5 to 3.0ºF
Increment
1ºF
1ºF
1ºF
1ºF
1ºF
1ºF
1ºF
5 minutes
30 minutes
0.5ºF
0.5ºF
0.5ºF
5 Min
5 Min
1
1
1ºF
1ºF
5 seconds
1ºF
5ºF
1ºF
2ºF
5ºF
60 Min
30 Sec
0.5ºF
0.5ºF
0.5ºF
0.5ºF