Table 10. Alert Codes and Troubleshooting
Alert
PRIORITY
Code
CONDITION
417
Critical
Moderate
IHarmony Damper
417
/ Critical
®
iComfort Wi-Fi
APPLICABLE
SYSTEM
ALERT TEXT
COMPONENTS
The outdoor unit discharge
sensor is either open, short-cir­
Outdoor unit
cuited or the temperature is out
of sensor range.
The damper control discharge
air temperature sensor is either
open, short-circuited or the
control module
temperature is out of sensor
range.
Critical alerts are displayed on the Home screen, in the Home­
owner alert button, and in the Installer alert button. Minor and
moderate alerts are found only in the Installer alert button.
COMPONENT OR SYSTEM OPERA­
TIONAL STATE AND TROU­
BLESHOOTING TIP
Outdoor unit control will not per­
form demand or time / tempera­
ture defrost operation. (System
will still heat or cool.)
Outdoor unit control detects open
or shorted sensor, or temperature
that is out of sensor range.
Critical alert after 10 minutes.
Reset by replacing sensor.
This fault is detected by allowing
the unit to run for 90 seconds be­
fore checking sensor resistance.
If the sensor resistance is not
within range after 90 seconds, the
board will count one fault.
After five faults, the outdoor con­
trol will lock out.
Check for proper sensor reading
and attachment to line.
Replace outdoor control if out-of-
specifications.
Outdoor control will not perform
any defrost tempering – moder­
ate condition.
The damper control module de­
tects open or shorted discharge
sensor, or temperature that is out
of discharge sensor range.
Check the resistance of the dis­
charge sensor and compare to
temperature resistance chart - re­
place if needed.
Reset by replacing the discharge
sensor.
This fault is detected by allowing
the unit to run for 90 seconds be­
fore checking discharge sensor
resistance.
If the discharge sensor resistance
is not within range after 90 sec­
onds, the control will count one
fault.
After five faults, the control will
lock out – critical condition.
Check for proper sensor reading
and attachment to line.
7-Day Programmable Communicating Thermostat
Page 59
HOW TO CLEAR
ALERT CODE
Automatically clears
when the system de­
tects that the issue no
longer exists.