Lennox iComfort Wi-Fi Setup Manual page 11

Touch screen programmable communicating thermostat
Hide thumbs Also See for iComfort Wi-Fi:
Table of Contents

Advertisement

Parameter Name:
Equipment Name
Electric Heating Airflow
High Cooling Airflow
Airflow Profile - Cooling
Continuous Indoor Blower Airflow
Heating Indoor Blower OFF Delay
Heating Indoor Blower ON Delay
Cooling Indoor Blower OFF Delay
Cooling Indoor Blower ON Delay
Note
All communicating Installer Parameters default CFM values based on DIP switch setting (non-communicating value) are calculated using the CFM
conversion tables and rounded up to closest number on 25 CFM resolution.
®
iComfort Wi-Fi
Table 5. System Devices > Air Handler
system devices
To adjust a setting,
System
highlight it, then press
Heat Pump
Edit
Air Handler
Air Handler
Thermostat
about
resetAll
edit
next
back
Default
Press edit to change name (up to 35
characters may be used).
Air Handler
Note: Pressing the resetALL button will
reset all custom parameter settings back
to factory default.
nnnn CFM (See Note at
NOTE: CFM Default and Values Settings
end of table)
are dependent on the tonnage of the unit
nnnn CFM (See Note at
NOTE: CFM Default and Values Settings
end of table)
are dependent on the tonnage of the unit
1: No Delays,
2: ON: No delays; OFF: 45 sec delay
1
3: ON: 82%/7.5min; OFF: No delays
4: ON: 50%/30s,82%/7.5min;
OFF:50%/30s
nnnn CFM (See Note at
NOTE: CFM Default and Values Settings
end of table)
are dependent on the tonnage of the unit
10 sec
0 sec
0 sec
2 sec
7-Day Programmable Communicating Thermostat
Page 11
Parameter Value Setting
0 to 10 Seconds
0 to 5 Seconds
0 to 30 Seconds
0 to 10 Seconds
Increment
5CFM
5CFM
10CFM
1 sec
1 sec
2 sec
1 sec