Lennox iComfort Wi-Fi Setup Manual page 49

Touch screen programmable communicating thermostat
Hide thumbs Also See for iComfort Wi-Fi:
Table of Contents

Advertisement

Table 10. Alert Codes and Troubleshooting
Alert
PRIORITY
Code
CONDITION
Furnace, air han­
180
Critical
dler or equipment
interface module
200
Critical
201
Critical
202
Critical
203
Critical
204
Critical
205
Critical
®
iComfort Wi-Fi
APPLICABLE
SYSTEM
ALERT TEXT
COMPONENTS
The thermostat has found a
problem with a system compo­
nent's outdoor temperature
sensor.
The furnace roll out limit switch
Furnace
is open.
The system has lost communi­
Furnace or air
cation with the indoor unit's
handler
blower motor.
The unit size code for the in­
Furnace or air
door unit and the size of blower
handler
motor do not match.
The unit size code for the in­
Furnace or air
door unit has not been select­
handler
ed.
There is an issue with the fur­
Furnace
nace gas valve.
The furnace gas valve relay
Furnace
contact is closed.
Critical alerts are displayed on the Home screen, in the Home­
owner alert button, and in the Installer alert button. Minor and
moderate alerts are found only in the Installer alert button.
COMPONENT OR SYSTEM OPERA­
TIONAL STATE AND TROU­
BLESHOOTING TIP
In normal operation after system
component control recognizes
sensors, the alarm will be sent if
valid temperature reading is lost.
Compare outdoor sensor resis­
tance to temperature / resistance
charts in unit installation instruc­
tions.
Replace sensor pack if neces­
sary.
At the beginning of (any) configu­
ration, furnace, air-handler control
or equipment interface module will
detect the presence of the sen­
sor(s).
If detected (reading in range), ap­
propriate feature will be set as 'in­
stalled' and shown in the 'About'
screen.
Correct the cause of roll out trip.
Reset roll out switch.
Test the furnace operation.
Lost communication with indoor
blower motor.
Possible causes include power
outage, brown-out, motor not
powered, loose wiring, condensa­
tion on system component control
without cover on breaker.
Problem may be on system com­
ponent control or motor side.
Incorrect appliance unit size code
selected.
Check for proper configuring un­
der unit size codes for furnace/air
handler on configuration guide or
in installation instructions.
Remove the thermostat from the
system while applying power and
reprogramming.
No system component unit size
code selected.
Check for correct configuration.
Unit size codes for furnace and
air handler are listed in the sys­
tem component configuration
guide or installation instruction.
Remove the thermostat from the
system while applying power and
reprogramming.
Check gas valve operation and
wiring.
Check wiring on control and gas valve.
7-Day Programmable Communicating Thermostat
Page 49
HOW TO CLEAR
ALERT CODE
Automatically clears
upon configuration, or
sensing normal val­
ues.
Automatically clears
after the furnace roll
out switch is closed.
Automatically clears
after communication is
restored.
Automatically clears
after the correct match
is detected following a
reset.
Automatically clears
after the correct match
is detected following a
reset.
Automatically clears
after the issue is cor­
rected.
Automatically clears
after the issue is cor­
rected.