Table 10. Alert Codes and Troubleshooting
Alert
PRIORITY
Code
CONDITION
418
Moderate
419
Critical
420
Critical
421
Critical
Moderate
422
Moderate /
423
Critical
507343-01
APPLICABLE
SYSTEM
COMPONENTS
Equipment inter
There is a faulty W output cir
face module and
cuit.
outdoor unit
Equipment inter
The W output has reported
face module and
more than five errors.
outdoor unit
Air handler or
The heat pump defrost cycle
has taken more than 20 min
equipment inter
utes to complete.
face module
Equipment inter
The W output terminal on the
face module and
outdoor unit is not wired cor
rectly.
outdoor unit
Compressor top cap switch ex
Outdoor unit
ceeding thermal limit.
The inverter has detected a cir
Outdoor unit
cuit issue.
Critical alerts are displayed on the Home screen, in the Home
owner alert button, and in the Installer alert button. Minor and
moderate alerts are found only in the Installer alert button.
COMPONENT OR SYSTEM OPERA
ALERT TEXT
Voltage sensed on W output terminal
when Y1 out is deactivated.
Page 60
TIONAL STATE AND TROU
BLESHOOTING TIP
W terminal is energized while in
cooling mode.
Possible cause may be a stuck
closed relay on the control, or
something external to the control
that is energizing W terminal
when it should not be energized.
Disconnect any wiring from the W
terminal.
If 24VAC is still on the terminal,
then it is a stuck relay.
If 24VAC disappears, then there
is a need to check any of the
wires hooked up to the W termi
nal.
The system will shut down the
outdoor unit.
The W output (code E418) on the
outdoor unit has reported more
than five strikes.
Disconnect thermostat lines from
W and verify 24VAC on the W.
If 24VAC is present, replace the
outdoor control.
Defrost cycle lasts longer than 20
minutes.
Check heat pump operation.
This is applicable only in commu
nicating indoor unit with non-com
municating heat pump.
Check condenser fan motor, TXV
and indoor unit blower motor.
Check for stuck reversing valve
or clogged refrigerant filter.
XC/XP25: Check to ensure that
one of the wires from the top cap
switch has not been disconnected
from one of the TP terminals on
the outdoor control. Reconnect
wire if disconnected.
When this condition is detected
the outdoor control will stop out
door unit operations and start the
anti-short cycle timer – moderate
condition.
Outdoor control will lockout unit
after 10 strikes within an hour –
critical condition.
HOW TO CLEAR
ALERT CODE
Automatically clears
after fault signal is re
moved.
Automatically clears
after power recycled.
Automatically clears
when W1 signal is re
moved.
Automatically clears
once voltage is not
sense on output for
power cycled.
Automatically clears
when error is corrected.
A moderate alarm
will clear automati
cally when the in
verter detects the
condition no longer
exist and will send
a clear alarm mes
sage.
To clear critical
alarm disconnect
power to outdoor
unit and restart.