Lennox iComfort Wi-Fi Setup Manual page 58

Touch screen programmable communicating thermostat
Hide thumbs Also See for iComfort Wi-Fi:
Table of Contents

Advertisement

Table 10. Alert Codes and Troubleshooting
Alert
PRIORITY
Code
CONDITION
412
Moderate
413
Critical
414
Critical
415
Critical
416
Critical
507343-01
APPLICABLE
SYSTEM
ALERT TEXT
COMPONENTS
The unit high-pressure is above
Outdoor unit
the required limit.
The high-pressure switch has
opened five times during a sin­
Outdoor unit
gle demand.
The discharge line temperature
is higher than the recommend­
Outdoor unit
ed upper limit of 279ºF.
The discharge line temperature
has been consistently higher
Outdoor unit
than the recommended upper
limit of 279ºF.
The outdoor coil sensor is ei­
ther open, short-circuited or the
Outdoor unit
temperature is out of sensor
range.
Critical alerts are displayed on the Home screen, in the Home­
owner alert button, and in the Installer alert button. Minor and
moderate alerts are found only in the Installer alert button.
COMPONENT OR SYSTEM OPERA­
TIONAL STATE AND TROU­
BLESHOOTING TIP
System is shut down
Unit high pressure is above the
upper limit.
The high pressure switch for
HFC­410A will open at 590PSIG
and close at 418PSIG.
Confirm that the system is proper­
ly charged with refrigerant.
Check outdoor fan motor, TXV,
indoor unit blower motor, stuck re­
versing valve and possible
clogged refrigerant filter.
Confirm that the outdoor unit is
clean.
Thermostat will shut down the
outdoor unit.
Open high pressure switch error
count reached five strikes.
Check system charge using ap­
proach and sub cooling tempera­
tures.
Check outdoor fan operation.
Check for dirt or debris blocking
air flow to outdoor unit.
Reset by putting outdoor unit con­
trol in test mode or resetting low
voltage power.
Discharge line temperature is
greater than 279ºF.
Make sure coil is clean and air­
flow unobstructed in and out of
condenser.
Check system operating pres­
sures and compare to unit charg­
ing charts in installation manual.
Discharge line high temperature
error count reached five strikes
during a single demand.
Make sure coil is clean and air­
flow unobstructed in and out of
condenser.
Check system charge using ap­
proach and sub cooling tempera­
tures.
Reset by putting outdoor control
in test mode or resetting low volt­
age power.
Outdoor unit control will not per­
form demand or time / tempera­
ture defrost operation. (System
will still heat or cool.)
Sensor being detected open or
shorted or temperature is out of
sensor range.
Page 58
HOW TO CLEAR
ALERT CODE
Automatically clears
after the high pressure
switch closes or a
power reset
Automatically clears
when the system de­
tects that the issue no
longer exists.
Automatically clears
after discharge tem­
perature is less than
225ºF.
Automatically clears
when the system de­
tects that the issue no
longer exists.
Automatically clears
when outdoor unit con­
trol detects proper
sensor readings.