Table 11. Troubleshooting Tips
No.
Issue / Problem
During the cooling mode the dis
played air volume on the indoor
19
control is substantially lower than
expected.
The Indoor unit is not providing
the expected air volume accord
20
ing to the cfm shown on the in
door unit control.
- No second stage cooling is
provided on a iComfort
door unit.
- Space temperature is above
second stage differential and
21
has run in first stage a long
time.
- No red Critical Alert icon or
alert is displayed in the
homeowner alert button.
22
No weather being displayed.
Unable to complete Wi-Fi router /
23
Internet connection
507343-01
Bold text indicates a button, or text display on the thermostat.
Possible Cause
The system may be following
"the cooling ramping" profile or
may be in "the Dehumidification
mode".
- Indoor unit air volume settings
®
in the iComfort
are not correct.
- System is operating in the
cooling mode and following
the cooling ramping profile or
dehumidification air volume.
®
out
The red Critical Alert icon and
homeowner alert button do not
display non-critical alerts.
®
iComfort Wi-Fi
not communic
ating with router.
Refer to 507037-01 Wi-Fi Troubleshooting checklist for iComfort Wi-Fi
- During the default cooling ramping profile the blower will run for 7.5
minutes at 82% of the cooling air volume. If the "cooling ramping
profile" is selected, the system will ramp to 100% after 7.5
minutes.
- The dehumidification mode will run the system at 70% of the cool
ing air volume which will be in addition to the air volume reduction
provided during the ramping profile. During the dehumidification
mode, a "d" will be displayed on the furnace or air handler control.
- In the installer program select the equipment button and choose
thermostat
the furnace or air handler from the system devices list and press
edit. Verify/set the correct air volume for heating and cooling
modes.
- If in the cooling mode check for cooling ramp mode or dehumidific
ation mode as in #18.
- Go to the installer program alert button to view all alerts and de
tails about those alerts.
- Look for alert code 401 (Compressor Long On Cycle) which indic
ates compressor ran more than 18 hours continuous and will lock
out 2nd stage compressor.
- Cycle indoor power off and back on, alert code 401 will clear within
a few minutes.
Make sure Wi-Fi is enabled.
Page 70
Corrective Action / Comments
®
thermostat.