9. Commissioning
4x
114492LTAL21H010a
fig. 21
Resetting factory setting
38

9.1.7 Resetting factory settings

• Press the  -key several times until the ˜ symbol flashes in
the menu bar;
• Select the installers menu using the  -key, 
appears in the display;
• Use the [-] -key or [+] -key to set installers code 0012;
• Confirm with the  -key;  appears;
• Press the [+] -key several times, df X appears;
• By default, the current value X for dF appears on the display; as
a check, compare this with the
value of X on the type plate; enter the value of X on the type
plate with the [-] key or the [+] key.
• Press the  key again, dU Y appears;
• By default, the current value Y for dU appears on the display;
as a check, compare this with the value of Y on the type plate;
enter the value of Y on the type plate with the [-] key or the [+]
key.
• Press the  key to confirm the values; the factory settings
have been reset.