4.7.4

Resetting to factory settings

4.8

Advanced settings

4.8.1

Service notification settings

Tab.15
Service notification parameter settings
Code
Display text
AP009
Service hours
AP010
Service notification
AP011
Service hours mains
4.8.2
Changing the ΔT setting
4.8.3

Settings for open-vented application

4.8.4

Screed drying

7837115 - v.01 - 10012023
4. Select Confirm to restore the commissioning settings.
You can reset the appliance to the default factory settings.
> Advanced Service Menu > Reset to Factory Settings
Use the rotary knob to navigate.
Use the
button to confirm your selection.
1. Press the
button.
2. Select Advanced Service Menu.
3. Select Reset to Factory Settings.
4. Select Confirm to restore the factory settings.
This appliance can notify the user when service is needed. The controls
will keep track of two counters:
The total of burner operating hours since the last service (AC002)
The total of hours on mains power supply since the last service (AC003)
When one of these counters meet the value set in parameters AP009 or
AP011, the user will be notified on the control panel.
Advice
Set this to a value that fits the operation conditions. Typically this is 3000 hours
for a commercial boiler in a normal heating set-up.
Set this to 1 = Custom notification as to use the values set in AP009 and AP011
Set this to a value that fits the operation conditions. Typically this is 8750 hours
(1 year) for a commercial boiler in a normal heating set-up.
The ΔT is factory set to 25 °C. It can be increased by a Remeha service
technician. Contact Remeha for more information.
Important
When increasing the ΔT, the control unit limits the flow
temperature to a maximum of 80 °C.
For this application, adjust the following parameter:
1. Set parameter DP006 to 0,0 bar.
2. Set parameter GP021 to 20°C.
The screed drying function is used to force a constant flow temperature or
a series of successive temperature levels to accelerate screed drying on
underfloor heating.
4 Installer instructions