Fault During Start-Up Procedure - REMEHA GAS 210-80 ECO PRO Technical Information

High efficiency low nox gas boiler
Hide thumbs Also See for GAS 210-80 ECO PRO:
Table of Contents

Advertisement

9. Commissioning
32
With a heat demand: 
1 Boiler starts
2 Burner starts
3 Central heating operation; briefly in part load then in full load
When a heat demand ceases:
5 Burner stops
6 Boiler stops
0 Stand-by mode
table 10
Normal operation

9.1.2 Fault during start-up procedure

If nothing appears on the display, check:
- the connection of the mains lead;
- the main fuse in the instrument box (F = 6.3 AT, 230 V);
- the fuse on the control unit (F1 = 1.6 AT, 230 V);
- the mains voltage.
• A fault code in the display is recognised as follows: the fault
symbol
appears and
the fault code flashes underneath it;
• The meaning of this fault code can be found in the fault table,
see Section 11.2.
• If possible, solve the fault first.
• Press the RESET key for 3 seconds to restart the Gas 210
ECO PRO.
If the display does not show RESET but SERVICE, the boiler must
be switched off and switched on again after 10 seconds before the
fault can be reset.
GAS 210 ECO PRO
114494-190310