6. Gas-side connections

6.1 Gas connection

6.2 Gas pressure

3+4 L
fig. 04
Gas multiblocks

6.3 Gas/air ratio control

114494-190310
The boiler is suitable for use with natural gas and propane* cat-
egory II
department. All gas appliances must, by law, be installed by com-
petent persons (e.g. Corgi). Failure to install appliances correctly
could lead to prosecution. It is in your own interest and that of
safety to ensure that the law is complied with.
The gas connection is at the top of the boiler . We recommend
installing a gas filter in the gas supply pipe to avoid pollution of the
gas multiblock. The gas filter's resistance must not be so high that
the minimum inlet gas pressure can no longer be achieved.
* Refer to Broag for using propane.
The boiler has been factory set and tested by Remeha to natural
5+6 L
gas (G20) - with an inlet pressure of 17 mbar .
The boiler is suitable for 17 - 30 mbar inlet gas pressure.
For propane (LPG), an inlet pressure of 37 - 50 mbar is required.
114492LTAL21H003a
The boiler has a zero governor gas valve. This gas valve main-
tains the ratio between the gas and air quantities in the burner at
a constant level under variable loads. This ensures clean and reli-
able combustion and high efficiency across the entire load range.
. For other types of natural gas, consult our Technical
2H3P
6. Gas-side connections
15