16. Application data

16. Application data

16.1 General

16.2 Air and flue gas application options

16.3 Hydraulic application options

16.4 Cascade application

66
The boiler is suitable for a wide range of applications. The boiler
offers numerous flue gas, hydraulic, gas and control applica-
tion options, but, at the same time, is not complicated to install.
This and its moderate dimensions, low noise levels and cascade
options mean the boiler can be installed almost anywhere (for
general legal requirements, see Section 13.2).
The choice of versions (open or closed combustion air supply)
provides excellent siting flexibility for the boiler . A motorised flue
gas discharge valve is available as an accessory and is used for
overpressure flue gas cascade arrangements.
The boiler is equipped with an enclosed housing that also serves
as an air box. An air filter and connection set are available for situ-
ations in which the boiler has to be commissioned during the con-
struction phase or has to operate in a heavily polluted environment
(this only applies to room ventilated versions).
Direct connection to structural ducts is not acceptable because
of condensation, see Chapter 7 for instructions and flue gas dis-
charge tables.
The advanced boiler control ( abc
resistance ensures that the boiler can be used in virtually any
hydraulic system.
The boiler is also suited for configuration in a cascade. For over-
pressure flue gas cascade arrangements, use our motorised flue
gas discharge valve (available as an accessory). This prevents
flue gas from flowing back to boilers that are not in operation. As a
result of the narrow width and depth of the boiler , a heat output of
400 kW (2 x Gas 210- 200) can be provided in a floor area of just
under 1.2 m
. A floor area of less than 3 m
2
room for service and maintenance. If necessary, consult our Tech-
nical department.
GAS 210 ECO PRO
) and relatively low hydraulic
®
is sufficient to include
2
114494-190310