9. Commissioning
Status 5t
Number
Status
0
Stand-by mode
1
Boiler starts (heat demand)
2
Burner starts
3
Burning on central heating operation
5
Burner stop
6
Boiler stop (end of heat demand)
8
Control stop
9
Shutdown
table 11
Settings at service level
34

9.1.3.1 Status and sub status

In the 'information menu'  the following status and sub status
numbers are displayed:
Number
Sub status
0
Stand-by mode
1
Anti-hunting
2
Open hydraulic valve
3
Start pump
4
Wait for the correct temperatures for burner start
10
Open external gas valve
11
Fan running
12
Open flue gas damper
13
Pre-ventilation
14
Wait for release signal
15
Burner on
16
VPS gas leakage control
17
For ignition
18
Main ignition
19
Flame detection
20
Intermediate ventilation
30
Temperature control
31
Limited temperature control (
32
Output control
33
Increase protection level 1
34
Increase protection level 2 (part load)
35
Increase protection level 3 (shut down)
36
Modulate up for flame control
37
Stabilisation time
38
Cold start
40
Burner off
41
Post ventilation
42
Fan running
43
Close flue gas damper
44
Stop fan
45
Close the external gas valve
60
Pump post circulation
61
Pump off
62
Close hydraulic valve
63
Start anti-hunting
0
Wait for burner start
1
Anti-hunting
xx
Shutdown xx

9.1.4 Adjusting the boiler to the system

The boiler's control parameters are set to the most common cen-
tral heating systems. With these settings, practically all central
heating systems will work well. However, the user or the installer
can optimise the parameters as he/she wishes.
Sub status 5u
∆T safety)
(control modulation)
GAS 210 ECO PRO
114494-190310