4. Installation
4.3 Installation and service clearances
1
50
1190
3
600
fig. 02
Boiler room installation options
12
Clearance of at least 60 cm is required at the front of the boiler .
However, we recommend a clearance of 1 m. W e recommend a
clearance of at least 40 cm above the boiler control panel, at least
5 cm on the left side and at least 25 cm on the right side in con-
nection with condensed water discharge. Install a gas cock in the
immediate vicinity of/above the boiler.
1490
250
2100
450
450
600
2
50
1190
2930
250
1190
4
1890
450
1190
114492LTAL21H002a
GAS 210 ECO PRO
250
250
114494-190310