The clearances listed below are Minimum distances unless otherwise stated:
A major cause of fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
decorative gas appliance be installed only in accordance with these instructions.
Firegear Outdoors® Key West™ Series

MINIMUM CLEARANCES TO COMBUSTIBLES

if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this decorative gas
appliance be installed only in accordance with these instructions.
Key West Series Clearance Requirements
Clearance:
Dimension
A: Back wall
17" (432mm)
B: Sidewall
17" (432mm)
C: Ceiling
45" (1143mm)
D
1
: Floor
D
2
: Floor
E: Alcove Width
84"(2134mm)
F: Alcove Depth
60" (1524mm)
Notes:
A
F
WARNING
Fire hazard is an extreme risk
Burner to back wall
Burner to sidewall
Burner to Ceiling
0"
When using supplied leveling legs or optional casters.
1"(25mm)
Unit Base to Floor
Wall to Wall (Minimum)
Front to Back Wall (Maximum)
0"
No Hearth Required
C
B
D
E
Alcove