SiBE18-821_C
3.5
Restart Standby
Restart is prohibited to prevent frequent power-on/off and to equalize pressure in the refrigerant
system.
Actuator
Compressor
Outdoor fan
Four way valve (Y1S)
Main electronic expansion valve (Y1E)
Subcooling electronic expansion valve
(Y3E)
Hot gas bypass valve (Y2S)
Ending conditions
3.6
Stopping Operation
Operation of the actuator is cleared up when the system is down.
3.6.1 When System is in Stop Mode
Compressor
Outdoor fan
Four way valve (Y1S)
Main electronic expansion valve (Y1E)
Subcooling electronic expansion valve (Y3E)
Hot gas bypass valve (Y2S)
Ending conditions
Function
Operation
OFF
Ta > 30°C: STEP 4
Ta ≤ 30°C: OFF
Former condition remains.
0 pls
0 pls
OFF
2 min.
Actuator
Remarks
Operation
OFF
OFF
Former condition remains.
0 pls
0 pls
OFF
Indoor unit thermostat is turned ON.
Special Control
87