SiBE18-821_C
Caution
DIP switch setting after changing main PCB (A1P) to spare part PCB
When you change the main PCB (A1P) to spare part PCB, please carry out the following setting.
Please Attach the Capacity Setting Adaptor corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
Capacity Setting Adaptor
(1)
(2)
(3)
Position of Attaching the Capacity Setting Adaptor
X51A
Position of Attaching
the Capacity Setting Adaptor
Test Operation and Field Settings
Capacity Class
CAPACITY SETTING ADAPTOR (for 100/J112)
4 (112)
5 (140)
CAPACITY SETTING ADAPTOR (for 125/J140)
6 (160)
CAPACITY SETTING ADAPTOR (for 140/J160)
Note
Field Settings
(R14078)
137