Indoor Heat Exchanger Thermistor (R3T) Abnormality - Daikin Super Multi Plus E-Series FTXG25EV1BW Service Manual

Table of Contents

Advertisement

Troubleshooting for SA Indoor Unit
5.7

Indoor Heat Exchanger Thermistor (R3T) Abnormality

C5
Remote
Controller
Display
Method of
The temperature detected by indoor heat exchanger thermistor (R3T)
Malfunction
Detection
Malfunction
When the indoor heat exchanger thermistor becomes disconnected or shorted while the indoor
unit is running.
Decision
Conditions
Supposed
Causes
Troubleshooting
Check the connection of
connector
Disconnect the thermistor
(R3T) from X17A on the
indoor unit PCB and measure
the resistance.
Refer to "Thermistor Resistance / Temperature Characteristics" table 2 on page 427.
370
Defective thermistor
Defective indoor unit PCB
Disconnection of connector
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
NO
Is it normal?
YES
Is the
NO
thermistor normal?
YES
SiBE18-821_C
Connect it correctly.
Replace the thermistor
(R3T).
Replace indoor unit
PCB.
(R13005)
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Super multi plus e-series ftxg35ev1bwSuper multi plus e-series ftxg25jv1bwSuper multi plus e-series ftxg35jv1bwSuper multi plus e-series ctxg50jv1bwSuper multi plus e-series bpmks967b2bSuper multi plus e-series bpmks967b3b ... Show all

Table of Contents