Troubleshooting for Outdoor Unit
Troubleshooting
416
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
U9
"
" has
been displayed for 2
minutes or more?
NO
Turn on all indoor units.
Does
UA
the "
"
display blinks on
the remote controllers of
other units within the
same refrigerant
system?
NO
Does
A1
the "
"
display blink on the
remote controllers of other
units within the same
refrigerant
system?
NO
Does
A9
the "
"
display blink on the
remote controllers of other
units within the same
refrigerant
system?
NO
Does
U4
the "
"
display blink on the
remote controllers of other
units within the same
refrigerant
system?
NO
YES
YES
YES
YES
YES
SiBE18-821_C
Re-diagnose by display after
passage of 2 minutes or
more.
Refer to troubleshooting for
UA
"
" error code.
Refer to troubleshooting for
A1
"
" error code.
Refer to troubleshooting for
A9
"
" error code.
Refer to troubleshooting for
U4
"
" error code.
Refer to troubleshooting for
U5
"
" error code.
(R13049)
Troubleshooting