Outdoor Unit
Step
2
Cut the clamp.
3
Remove the 4 screws
and remove the fan
motor.
444
Procedure
Fan
motor
D-cut
Mount the fan motor with its mark " "
positioned toward the bottom.
Lead wire for
fan motor
(R9243)
Earth wire
Clamp
(R9244)
SiBE18-821_C
Points
Pull out the connector while
supporting the fan motor and
pushing the engaging hook,
without pulling its lead wires.
When reassembling, put the
fan motor lead wire through
the back of the fan motor (so
as not to be entangled with
the outdoor fan).
Lead wire
Outdoor fan
(R3249)
Be sure to remove the lower
screws first. If the upper
screws are removed first, the
fan motor, the center of
gravity of which is toward the
front, may tilt down or fall,
getting you injured.
Removal Procedure