Daikin P Series Technical Manual

Daikin P Series Technical Manual

Split unit air conditioner wall mounted series

Advertisement

R410A
TECHNICAL MANUAL
Split Unit Air Conditioner
Wall Mounted P/QS/PS Series
FTN-P/QS/PS Series
— Cooling Only [50Hz] —
P Series
QS Series
PS Series
TM-FTN-0916-B

Advertisement

Table of Contents
loading

Summary of Contents for Daikin P Series

  • Page 1 R410A TECHNICAL MANUAL Split Unit Air Conditioner Wall Mounted P/QS/PS Series FTN-P/QS/PS Series — Cooling Only [50Hz] — P Series QS Series PS Series TM-FTN-0916-B...
  • Page 2: Table Of Contents

    Table of Contents Table of Contents Nomenclature........................2 Indoor ..........................2 Outdoor ..........................2 Product Line-Up ......................3 Application Information .....................5 Operating Range ......................5 Refrigerant Circuit Diagrams ..................6 Installation Guideline .....................8 Sound Data ........................13 Sound Pressure Level ....................13 NC Curve ........................14 Engineering & Physical Data ...................17 Performance Data ......................21 Calculation Steps ......................21 Performance Tables .....................24...
  • Page 3: Nomenclature

    FT N 10 P Controller L/I: Wireless Controller M/J: Wired Controller Power Supply V1: 220-240V 1 Phase 50Hz Product Series P: P Series QS: QS Series Capacity* 10: 10,000 Btu/hr 15: 15,000 Btu/hr 20: 20,000 Btu/hr 25: 25,000 Btu/hr 30: 30,000 Btu/hr...
  • Page 4: Product Line-Up

    Nomenclature Product Line-Up Indoor Unit Classification Nomenclature FTN10QSV1I FTN15QSV1I FTN20QSV1I FTN25QSV1I FTN10QSV1J FTN15QSV1J FTN20QSV1J FTN25QSV1J FTN10PV1L FTN15PV1L FTN20PV1L FTN25PV1L FTN30PSV1L FTN35PSV1L FTN10PV1M FTN15PV1M FTN20PV1M FTN25PV1M FTN30PSV1M FTN35PSV1M...
  • Page 5 Nomenclature Outdoor Unit Classification Nomenclature RN10FV1 RN15FV1 RN20CV1 RN25CV1 RN25CHV1 RN30CV1 RN35DV1 RN10FGV1 RN15FGV1 RN20CGV1 RN25CGV1 RN25CHGV1 RN30CGV1 RN35DGV1...
  • Page 6: Application Information

    Application Information Application Information Operating Range Ensure the operating temperature is in allowable range. Cooling Cooling The use of your air conditioner outside the range of working temperature and humidity can result in serious failure. INDOOR TEMP. WB (°C)
  • Page 7: Refrigerant Circuit Diagrams

    Application Information Refrigerant Circuit Diagrams Model: FTN10P/QS - RN10F / FTN15P/QS - RN15F / FTN20P/QS - RN20C / FTN25P/QS - RN25C/CH Model: FTN30PS - RN30C...
  • Page 8 Application Information Model: FTN35PS - RN35D...
  • Page 9: Installation Guideline

    Application Information Installation Guideline Sharp edges and coil surfaces are potential injury hazard. Avoid from contact with them. Installation Diagram Indoor unit Caulk pipe Cut thermal insulation pipe 75mm or more from ceiling hole gap to an appropriate length and with putty.
  • Page 10 Application Information Outdoor Clearance If the condensing unit is operated in an atmosphere containing oils (including machine oils), salt (coastal area), sulphide gas (near hot spring, oil refinery plant), such as substances may lead to failure of the unit. The outdoor unit must be installed in such a way, so as to prevent short circuit of the hot discharged air or obstruction to the smooth air fl ow.
  • Page 11: Cable Size

    Application Information Cable Size FTN20/25P/QS Indoor FTN10/15P/QS FTN35PS FTN30PS Model RN10/15C RN20/25C Outdoor RN10/15F RN35D RN25CH RN30C Power supply cable size Number of wire Interconnection cable size Number of wire Recommended fuse...
  • Page 12: Refrigerant Piping

    Application Information Refrigerant Piping Piping Length and Elevation When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases, system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity, and as the result the compressor may become defective.
  • Page 13: Additional Charge

    Application Information Additional Charge • The refrigerant gas is charged in the outdoor unit and, if the piping length is 7.5m, additional charge of the refrigerant after vacuuming is not necessary. • When the piping length is more than 7.5m, additional refrigerant charge (g) per additional 1m length as tabulated: Indoor FTN10/15P/QS...
  • Page 14: Sound Data

    Sound Data Sound Data Sound Pressure Level 1/1 Octave A-weighted Sound Pressure Level (dB, ref 20µPa) Overall Noise Model Speed (dBA) Criteria 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz Turbo High FTN10P/QS Quiet Turbo High FTN15P/QS Quiet Turbo High FTN20P/QS Quiet Turbo High...
  • Page 15: Nc Curve

    Sound Data NC Curve FTN10P/QS NC-70 NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz) FTN15P/QS NC-70 NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz)
  • Page 16 Sound Data FTN20P/QS NC-70 NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz) FTN25P/QS NC-70 NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz)
  • Page 17 Sound Data FTN30/35PS NC-70 NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 1000 2000 4000 8000 Octave-band frequency (Hz)
  • Page 18: Engineering & Physical Data

    Engineering & Physical Data Engineering & Physical Data Engineering Data (P/PS Series) INDOOR UNIT FTN10PV1 FTN15PV1 FTN20PV1 MODEL OUTDOOR UNIT RN10FV1 RN15FV1 RN20CV1 Btu/h 9500 12000 18000 NOMINAL COOLING CAPACITY 2784 3517 5275 NOMINAL TOTAL INPUT POWER 1105 1835 NOMINAL RUNNING CURRENT 3.86 4.94 8.10...
  • Page 19 Engineering & Physical Data INDOOR UNIT FTN25PV1 FTN25PV1 FTN30PSV1 FTN35PSV1 MODEL OUTDOOR UNIT RN25CV1 RN25CHV1 RN30CV1 RN35DV1 Btu/h 22000 24000 30000 33000 NOMINAL COOLING CAPACITY 6448 7034 8792 9672 NOMINAL TOTAL INPUT POWER 2060 2140 2900 3660 NOMINAL RUNNING CURRENT 9.14 9.32 13.50...
  • Page 20 Engineering & Physical Data Engineering Data (QS Series) INDOOR UNIT FTN10QSV1 FTN15QSV1 FTN20QSV1 MODEL OUTDOOR UNIT RN10FV1 RN15FV1 RN20CV1 Btu/h 9500 12000 18000 NOMINAL COOLING CAPACITY 2784 3517 5275 NOMINAL TOTAL INPUT POWER 1105 1835 NOMINAL RUNNING CURRENT 3.86 4.94 8.10 Btu/h/W 10.92...
  • Page 21 Engineering & Physical Data INDOOR UNIT FTN25QSV1 FTN25QSV1 MODEL OUTDOOR UNIT RN25CV1 RN25CHV1 Btu/h 22000 24000 NOMINAL COOLING CAPACITY 6448 7034 NOMINAL TOTAL INPUT POWER 2060 2140 NOMINAL RUNNING CURRENT 9.14 9.32 Btu/h/W 10.68 11.22 REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAPILARY TUBE REFRIGERANT CHARGE 1.70 1.65...
  • Page 22: Performance Data

    Performance Data Performance Data Calculation Steps Interpolation method can be used to get the total cooling capacity, TC and sensible cooling capacity, SC and power input, PI at those temperatures which are not stated out in the table. Extrapolation method is not allowed to be used.
  • Page 23 Performance Data Details of Calculation: By Interpolation Method 25°C – 24°C – 1.80kW ⇒ Step: 27°C – 24°C 1.83kW – 1.80kW To obtain the TC, SC & PI for ⇒ x = 1.81kW (a) Indoor Condition: 25°C DB, 16°C WB Similarly, Outdoor Condition: 35°C DB = 1.75kW...
  • Page 24 Performance Data Step: To obtain the TC, SC & PI for (a) Indoor Condition: 25°C DB, 17°C WB Outdoor Condition: 37°C DB Outdoor temperature 35°C 37°C 40°C 1.87 1.63 0.63 1.74 1.52 0.68 By Interpolation Method Similarly, 37°C – 35°C x –...
  • Page 25: Performance Tables

    Performance Data Performance Tables Model: FTN10P/QS - RN10F Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 2.62 2.03 0.66 2.53 1.98 0.71 2.44 1.92 0.77 2.34 1.87 0.84 2.15 1.74 0.91 1.98 1.64 1.00 24°C 2.63 2.43 0.66 2.53 2.37 0.72 2.44 2.32 0.77 2.34 2.26 0.84 2.15 2.11 0.91 1.99 1.99 1.00 16°C 27°C 2.65 2.65 0.66 2.56 2.56 0.72 2.47 2.47 0.78 2.38 2.38 0.84 2.19 2.19 0.91 2.04 2.04 1.01...
  • Page 26: Ftn15P/Qs

    Performance Data Model: FTN15P/QS - RN15F Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 3.32 2.35 0.84 3.20 2.28 0.91 3.08 2.22 0.98 2.96 2.16 1.07 2.71 2.01 1.16 2.51 1.89 1.28 24°C 3.32 2.81 0.84 3.20 2.74 0.91 3.08 2.68 0.98 2.96 2.61 1.07 2.72 2.44 1.16 2.52 2.30 1.28 16°C 27°C 3.35 3.18 0.84 3.23 3.11 0.91 3.12 3.04 0.99 3.00 2.96 1.07 2.77 2.76 1.16 2.58 2.58 1.28...
  • Page 27 Performance Data Model: FTN20P/QS - RN20C Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 4.97 3.57 1.39 4.80 3.47 1.51 4.62 3.38 1.63 4.43 3.28 1.77 4.07 3.06 1.92 3.76 2.87 2.12 24°C 4.98 4.27 1.39 4.80 4.17 1.51 4.63 4.08 1.63 4.44 3.97 1.77 4.08 3.71 1.92 3.77 3.50 2.12 16°C 27°C 5.02 4.84 1.40 4.85 4.73 1.51 4.68 4.62 1.64 4.51 4.50 1.78 4.16 4.16 1.93 3.87 3.87 2.13...
  • Page 28 Performance Data Model: FTN25P/QS - RN25C Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 6.08 4.30 1.57 5.86 4.19 1.69 5.65 4.08 1.83 5.42 3.96 1.99 4.98 3.69 2.16 4.60 3.47 2.38 24°C 6.09 5.15 1.57 5.87 5.03 1.69 5.65 4.92 1.83 5.43 4.79 1.99 4.99 4.48 2.16 4.61 4.22 2.38 16°C 27°C 6.14 5.84 1.57 5.93 5.71 1.70 5.72 5.57 1.84 5.51 5.43 1.99 5.08 5.05 2.16 4.73 4.73 2.39...
  • Page 29 Performance Data Model: FTN25P/QS - RN25CH Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 21°C 6.63 4.69 1.63 6.39 4.57 1.76 6.16 4.44 1.90 5.91 4.32 2.07 5.43 4.02 2.24 5.01 3.78 2.47 24°C 6.64 5.62 1.63 6.40 5.49 1.76 6.16 5.36 1.91 5.92 5.23 2.07 5.44 4.88 2.24 5.03 4.61 2.47 16°C...
  • Page 30 Performance Data Model: FTN30PS - RN30C Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 8.29 5.94 2.20 7.99 5.79 2.38 7.70 5.63 2.58 7.39 5.47 2.80 6.78 5.09 3.04 6.26 4.79 3.35 24°C 8.30 7.11 2.20 8.00 6.95 2.38 7.71 6.79 2.58 7.40 6.62 2.80 6.80 6.18 3.04 6.29 5.83 3.35 16°C 27°C 8.36 8.07 2.21 8.09 7.88 2.39 7.80 7.70 2.59 7.51 7.50 2.81 6.93 6.93 3.05 6.44 6.44 3.36...
  • Page 31 Performance Data Model: FTN35PS - RN35D Cooling Mode Outdoor temperature 19°C 25°C 30°C 35°C 40°C 46°C (CFM) 21°C 9.12 6.54 2.78 8.79 6.36 3.01 8.47 6.19 3.26 8.13 6.02 3.53 7.46 5.60 3.83 6.89 5.27 4.22 24°C 9.13 7.83 2.78 8.80 7.65 3.01 8.48 7.47 3.26 8.14 7.28 3.53 7.48 6.80 3.83 6.92 6.42 4.23 16°C 27°C 9.20 8.87 2.79 8.89 8.67 3.01 8.58 8.47 3.26 8.26 8.25 3.54 7.62 7.62 3.84 7.09 7.09 4.24...
  • Page 32: Outline & Dimension

    Outline & Dimension Outline & Dimension Indoor Unit Model: FTN10/15/20/25P THE MARK SHOWS PIPING DIRECTION REAR REAR LEFT RIGHT TOP VIEW NAME PLATE SIGNAL RECEIVER TERMINAL BLOCK WITH INDOOR UNIT EARTH ON/OFF SWITCH SIDE VIEW BOTTOM BOTTOM TERMINAL ROOM TEMPERATURE LOUVER FRONT GRILLE FIXED SCREWS THERMISTOR (INSIDE) (INSIDE)
  • Page 33 Outline & Dimension Recommended mounting plate retention spots (7 spots in all) Through the wall hole Ø 65mm Liquid pipe end Gas pipe end Drain hose position INSTALLATION PLATE 20/25 Dimension Model 1065 310 228 190 173 219 580 20/25P Note: Dimension in mm...
  • Page 34 Outline & Dimension Model: FTN-10/15/20/25QS THE MARK SHOWS PIPING DIRECTION REAR REAR LEFT RIGHT TOP VIEW STICKER SERIAL NO. SIGNAL RECEIVER TERMINAL BLOCK WITH INDOOR UNIT ON/ OFF SWITCH EARTH BOTTOM BOTTOM TERMINAL LOUVER ROOM TEMPARATURE FRONT GRILLE THERMISTOR (INSIDE) FIXED SCREWS (INSIDE) SIDE VIEW...
  • Page 35 Outline & Dimension Recommended mounting plate retention spots (7 spots in all) Through the wall hole Ø 65mm Liquid pipe end Gas pipe end Drain hose position INSTALLATION PLATE 20/25 Dimension Model 1124 310 237 190 173 219 580 20/25QS Note: Dimension in mm...
  • Page 36 Outline & Dimension Model: FTN30/35PS Dimension Model 1289 310 240 201 193 196 177 650 30/35PS Note: Dimension in mm...
  • Page 37: Outdoor Unit

    Outline & Dimension Outdoor Unit Model: RN10/15F Dimension Model 550 658 51 11 273 16 14 470 96 14 133 10 299 10/15F Note: Dimension in mm Model: RN20/25C/CH Model: ARYN20/25/35LV1 Dimension Model 855 628 328 520 179 46 93 149 101 113 603 126 164 15 20/25C 855 730 328 520 179 46 93 149 101 113 603 126 164 15...
  • Page 38 Outline & Dimension Model: RN30C Dimension Model 855 730 328 520 182 44 93 149 101 113 603 126 164 15 34 23 73 75 362 Note: Dimension in mm Model: RN35D Model: ARYN20/25/35LV1 Dimension Model 1030 826 400 695 57 40 746 142 26 448 22 Note: Dimension in mm...
  • Page 39: Wiring Diagram

    Wiring Diagram Wiring Diagram Outdoor Unit Indoor Unit Model: RN10/15F Model: FTN10/15P 220-240V 1 Ph 50 Hz...
  • Page 40 Wiring Diagram Indoor Unit Outdoor Unit Model: FTN20/25P, FTN30PS Model: RN20/25/30C POWER SUPPLY 220-240V ,1 Ph, 50 Hz...
  • Page 41 Wiring Diagram Indoor Unit Outdoor Unit Model: FTN35PS Model: RN35D POWER SUPPLY 220-240V ,1 Ph, 50 Hz...
  • Page 42 Wiring Diagram Indoor Unit Outdoor Unit Model: FTN10/15QS Model: RN10/15F 220-240V 1 Ph 50 Hz...
  • Page 43 Wiring Diagram Indoor Unit Outdoor Unit Model: FTN20/25QS Model: RN20/25C/CH 220-240V 1 Ph 50 Hz...
  • Page 44: Service & Maintenance

    Service & Maintenance Service & Maintenance • Disconnect from main supply before servicing the air conditioner. • The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention. Components Maintenance Procedures Period...
  • Page 45: Troubleshooting

    Troubleshooting Troubleshooting Indicator Lights IR Signal Receiver When an infra red remote control operating signal has been transmitted, the signal receiver on the indoor unit will respond as below to confirm acceptance of the signal transmission. ON to OFF 1 Long Beep OFF to ON 2 Short Beep Pump down/Cool force on...
  • Page 46 Troubleshooting LED Indoor Lights (Applicable for P/PS series): Normal Operation and Fault Conditions for Cooling Unit Error Normal Operation / Action Code Fault Indication COOL (GREEN) Cool mode Green Timer on Sleep mode on Fan mode on Dry mode on Blink E1 Room air sensor contact loose / short Call your dealer 1 time...
  • Page 47 Troubleshooting LED Indoor Lights (Applicable for QS series): Normal Operation and Fault Conditions for Cooling Unit Operation / Fault Indication SLEEP COOL TIMER (RED) (BLUE) (ORANGE) Cooling mode Blue Timer on Sleep mode on Fan mode on Blue Dry mode on Blue Error indication Blue...
  • Page 48 Troubleshooting Error Code Diagnosis (Applicable for QS series) SWING TURBO MODE QUIET SLEEP TIMER ON TIMER CANCEL CANCEL CLOCK CANCEL OFF TIMER CANCEL Diagnosis Step 1. Hold down ON TIMER CANCEL button or OFF TIMER CANCEL button for 5 seconds, a “ ”...
  • Page 49 w w w. d a i k i n . c o m . m y...

This manual is also suitable for:

SeriesQsFtn-p seriesPs series