Programming the Control
Communications ID Numbers – Displays programmed SIM card information
Message
MAC:
xxxxxxxxxxxx
MAC CRC:
xxxx
WiFi:*
xxxxxxxxxxxx
WiFi Ver:
x.x.x
SCID:**
xxxxxxxxxxxxxxxxxxxx
IMEI:**
xxxxxxxxxxxxxxx
* This is the system MAC that should be referenced whenever speaking with technical support.
** Displayed if GSM communication path is enabled.
Test Communications – Performs network diagnostics and sends test alarms to AlarmNet. The following
tests are available depending on the type of communications module installed.
Test Ethernet
This test is available if IP communication path is enabled. The network diagnostic process tests the integrity of the links
between the LYNX Touch and the various connection points of AlarmNet Control that are known as "Redirectors". If a physical
link is detected and is ready, the following diagnostics are performed.
Testing Gateway...
Traces the connection to the Gateway and displays the following:
Testing Gateway – Successful!
Testing Gateway – Failed!
Testing Redirector * Sequentially traces the connection to Redirector 1, 2 and 3 at AlarmNet Control. The following will be
displayed.
Redirector * – Service OK
Redirector * – Failed
* = Number of the director being tested is displayed
A summary of the tests is displayed after Redirector 3 is tested. The example shows that the tests of all three
connection points, or Redirectors, were successful. If an error occurred at any point, the summary will display "Failed"
next to the faulty Redirector.
Redirector 1 – Service OK
Redirector 2 – Service OK
Redirector 3 – Service OK
If no physical link is detected, the test is aborted and one of the following is displayed:
No Physical Link
Link Not Ready
Send Any
If both IP and GSM communication paths are enabled and the LYNX Touch is registered, a Test alarm is sent over IP path. If
that is not successful, it sends the alarm over GSM path and the following message is displayed: Test Message Sent
If the device is not registered, the following is displayed: Test Message Failed – Not Registered
Send GSM Message
If GSM communication path is enabled and the LYNX Touch is registered, a Test alarm to AlarmNet over the GSM path. The
following message is displayed: Test Message Sent
If the device is not registered, the following message is displayed: Test Message Failed – Not Registered
Send Ethernet Message
If IP communication path is enabled and the LYNX Touch is registered, a Test alarm to AlarmNet over the IP path. The
following message is displayed: Test Message Sent
If the device is not registered, the following message is displayed: Test Message Failed – Not Registered
Setup Communication – Performs registration of the LYNX Touch and its associated communication
module with AlarmNet updates configuration files or reset factory defaults.

Registering the LYNX Touch

Once the LYNX Touch is initialized and a communications module is programmed, it must be registered to
enable the account. Upon completion of the registration process, the LYNX Touch transmits a registration
message and receives a registration validation indicating that the account is now enabled. Wait for the
"Registration Success" message to appear, regardless of which registration method is used.
You can register the communications module by one of the following methods:
• Through the AlarmNet Direct website
• By Phone
• Through the LYNX Touch Diagnostics
MAC Address indicates the unique identification number for installed
communications module(s)
MAC CRC number for installed communications module(s)
Physical MAC Address of the WiFi module
WiFi module software version
Displays the ID number assigned to the installed SIM card (SCID)
Displays the ID number assigned to the installed GSM module.
A successful trace to Gateway. OR
Failed to reach Gateway.
Service at AlarmNet Control on Redirector 1, 2 or 3 is functioning. OR
Error occurred on Redirector 1, 2 or 3.
No physical link is detected.
There is a link but it is not ready (address not resolved).