Honeywell LYNX Touch L5210 Series Programming Manual
Honeywell LYNX Touch L5210 Series Programming Manual

Honeywell LYNX Touch L5210 Series Programming Manual

Hide thumbs Also See for LYNX Touch L5210 Series:

Advertisement

Quick Links

LYNX Touch
L5210/L7000 Series
Security System
Programming Guide
800-19976
12/14 Rev. B
L5210/L7000

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell LYNX Touch L5210 Series

  • Page 1 LYNX Touch L5210/L7000 Series Security System Programming Guide 800-19976 12/14 Rev. B L5210/L7000...
  • Page 2: Table Of Contents

    Table of Contents Entering Programming Mode ............................ 3 Programming the Data Fields ........................... 3 Loading a Default Set ..............................3 Exiting Programming Mode ............................3 Data Fields ................................4 Change Installer Code ............................4 Program System Type ............................4 Program Date and Time ............................5 Program Communications .............................
  • Page 3: Entering Programming Mode

    Entering Programming Mode You may find it convenient to adjust the volume setting before entering the Programming Mode. This will allow you to clearly hear feedback announcements or system beeps. 1. Power-up the control and allow it to “boot-up”. “System Standby” is displayed on the touch screen. When the “boot-up”...
  • Page 4: Data Fields

    Screen Display Function & Programming Options DATA FIELDS Note: Preprogrammed defaults are shown on the screen display. Change Installer Code Installer Code Installer Code Enter 4 digits [The defaulted Installer Code is 4112] 5000-100-129-V0 Program System Type RF Jam RF Jam Disabled Disabled RF Jam Log...
  • Page 5: Program Date And Time

    Screen Display Function & Programming Options Events – Log Trouble Events – Log Trouble Enabled Enabled Disabled Non Security Non Security Enabled Enabled Disabled Remote Access Serial Remote Access Serial Enabled Disabled Disabled Note: If the “Remote Access Serial” option is enabled, you will be prompted to select a “Multi Mode Serial”.
  • Page 6: Program Communications

    Screen Display Function & Programming Options Start Week End Week First First Second Third Fourth Last Next to Last 3rd from Last Program Communications Communicator Program the following options: Communicator Communications Path City ID CS ID Sub ID 5000-100-132-V0 Supervision Old Alarm Time Remote Acc.
  • Page 7: Program Zones

    Screen Display Function & Programming Options IP Fault Time (min) (displayed if IP or WiFi is selected as Communications Path) IP Fault Time (min) Enter 2-digits 00-99 Use DHCP Use DHCP Note: If disabled the following options will be active. NIC IP Address (Appears only if “no”...
  • Page 8 Screen Display Function & Programming Options Serial Number Serial Number When “Serial Number” has been selected “Enter Serial Number or Activate” is displayed. The transmitter serial number and loop number can be enrolled via RF transmission OR manually. Enroll via RF Learning To enroll the device using RF Learning mode three transmissions (open/close) of the device will be required.
  • Page 9: Program Keys

    Screen Display Function & Programming Options Program Keys Keys Keys Select from the following options: Edit Add New Delete If add new is selected the following options can be programmed: Key Type User Serial Number Zone Button Key 1 – Zn 140 Button Key 2 –...
  • Page 10: Program Reporter

    Screen Display Function & Programming Options Program Reporter Reporter Reporter Note: The Follow Me Phone features are not available on the LYNX Touch L7000. Program the following options: Primary CS Info Secondary CS Info Follow Me Phone 1 Follow Me Phone 2 Report Selection Options Downloader...
  • Page 11 Screen Display Function & Programming Options Secondary Central Station Information Secondary CS Info Phone Type Communicator Type Phone Type Phone Type None None Contact Id: 4 Digit Contact Id: 10 Digit Note: If SIA, Contact Id: 4 Digit or Contact Id: 10 Digit is selected, the Phone Number and Account Number options will be displayed.
  • Page 12 Screen Display Function & Programming Options Phone Type (This feature is not available on the LYNX Touch L7000) Phone Type None None Follow Me (If Follow Me is selected several new options will be displayed) Phone Number (This feature is not available on the LYNX Touch L7000) Phone Number Enter the Follow Me Phone Number None...
  • Page 13 Screen Display Function & Programming Options Report Selection Report Selection Choose from the following options: Arm Away Arm Stay Bypass Bypass Restore Disarm Exit Error AC Loss AC Loss Restore Recent Closing Event Log Full Low Battery Low Battery Restore Trouble Trouble Restore RF Low Battery...
  • Page 14 Screen Display Function & Programming Options Low Battery Restore Low Battery Disabled Enabled Enabled Low Battery Restore Low Battery Restore Disabled Enabled Enabled RF Low Battery RF Low Battery Disabled Enabled Enabled RF Low Battery Restore RF Low Battery Restore Disabled Enabled Enabled...
  • Page 15: Program Sounder

    Screen Display Function & Programming Options Note: The Remote Phone feature is not available on the LYNX Touch L7000. Modem Speed Modem Speed Slow (Future Use) Note: The Remote Phone feature is not available on the LYNX Touch L7000. Ans. Machine Defeat Answering Machine Defeat (If No is selected the Ring Counter Option will be displayed.) Ring Counter (displayed if Ans.
  • Page 16: Program System Settings

    Screen Display Function & Programming Options Program System Settings System Settings System Settings Choose from the following options: Entry Delay 1 Entry Delay 1 Exit Delay Backlight Timeout Quick Arm Quick Exit Restart Exit Time Force Bypass Exit Warning Auto Stay Arming Lack of Usage Notify Power-up in Previous Display Alarm Cancel...
  • Page 17: Program The Z-Wave Module

    Screen Display Function & Programming Options Lack of Usage Notify Lack of Usage Notify Disabled Disabled 1 Day 7 Days 27 Days 90 Days 180 Days 365 Days Power-Up in Previous State Power-Up in Previous Always Enabled (not selectable) Display Alarm Cancel Display Alarm Cancel Display Exit Time Display Exit Time...
  • Page 18: Communication Diagnostics

    Communications Diagnostics Note: For additional information regarding these fields, refer to the LYNX Touch Installation and Setup Guide P/N 800-19974 or higher. Communication Diagnostics Comm. Diagnostics Choose from the following options (depending upon the Communication Module that is installed: Communication Ethernet Status Information...
  • Page 19 Communications Diagnostics Test Communication - Performs network diagnostics and sends test alarms to the network. The following tests are available depending on the type of communications module installed. Message Function Send Cellular Message: Available if Cellular communication path is enabled Test Ethernet: Available if IP or WiFi communication path is enabled Send Ethernet Message:...
  • Page 20: Zone Programming Worksheet

    Zone Programming Worksheet Fill in the required data on this worksheet, then follow the programming procedure. (The defaults shown are for Configuration 1) See Explanation of Zone Assignment Table Headings Note: Zones 65-70, 156-163, and 186-187 are only available on the LYNX Touch L7000 control. Zone Loop Device...
  • Page 21 Zone Programming Worksheet Zone Loop Device Response Transmitter Zone Type Type Report Chime Supervision Night Serial Number Descriptor Not Used Standard Supervised Main Not Used Standard Supervised Main Not Used Standard Supervised Main Not Used Standard Supervised Main 4 Button Arm Away Disabled Button...
  • Page 22 Zone Programming Worksheet Zone Loop Device Response Transmitter Zone Type Type Report Chime Supervision Night Serial Number Descriptor Temperature Monitor Disabled High Temp Monitor Temperature Disabled Low Temp Monitor Temperature Disabled High Temp Monitor Temperature Disabled Low Temp Monitor Temperature Disabled High Temp Monitor...
  • Page 23: 5800 Series Transmitter Loop Numbers Diagram

    5800 Series Transmitter Loop Numbers LOOP 1 LOOP 1 (LOW (LOW SENSITIVITY SENSITIVITY LOOP LOOP 2 LOOP 2 (HIGH (HIGH LOOP 1 SENSITIVITY) SENSITIVITY) LOOP LOOP 3 (TEMP) LOOP 3 (TEMP) LOOP 4 (TAMPER) LOOP 4 (TAMPER) 5 8 0 0 C O 5 8 0 0 M i c r a 5 8 0 0 P I R - R E S 5 8 0 0 P I R / 5 8 0 0 P I R - C O M...
  • Page 24: Lynx Touch L5210 Programming Default Values

    L5210 Programming Default Values Program Function Configuration 1 Configuration 2 Configuration 3 Configuration 4 Installer Code 4112 4112 4112 4112 System Type RF Jam Disabled Disabled Disabled Disabled Speaker Phone Disabled Disabled Disabled Disabled Two Way Voice Disabled Disabled Disabled Disabled RF House Code Phone Notification...
  • Page 25 Program Function Configuration 1 Configuration 2 Configuration 3 Configuration 4 Dynamic Priority None None None None Dynamic Delay None None None None Report All Press to Report All Press to Report All Press to Report All Press to Report All Report Alarms Enabled Enabled...
  • Page 26 Program Function Configuration 1 Configuration 2 Configuration 3 Configuration 4 Low Battery Enabled Enabled Enabled Enabled Low Battery Restore Enabled Enabled Enabled Enabled RF Low Battery Enabled Enabled Enabled Enabled RF Low Battery Restore Enabled Enabled Enabled Enabled Options Blank Blank Blank Blank...
  • Page 27: Lynx Touch L7000 Programming Default Values

    L7000 Programming Default Values Program Function Configuration 1 Configuration 2 Configuration 3 Configuration 4 Installer Code 4112 4112 4112 4112 System Type RF Jam Disabled Disabled Disabled Disabled Speaker Phone Disabled Disabled Disabled Disabled Two Way Voice Disabled Disabled Disabled Disabled RF House Code Phone Notification...
  • Page 28 Program Function Configuration 1 Configuration 2 Configuration 3 Configuration 4 Account Number FFFF FFFF FFFF FFFF Dynamic Priority None None None None Dynamic Delay None None None None Report All Press to Report All Press to Report All Press to Report All Press to Report All Report Alarms Enabled...
  • Page 29 Program Function Configuration 1 Configuration 2 Configuration 3 Configuration 4 AC Loss Restore Enabled Enabled Enabled Enabled Low Battery Enabled Enabled Enabled Enabled Low Battery Restore Enabled Enabled Enabled Enabled RF Low Battery Enabled Enabled Enabled Enabled RF Low Battery Restore Enabled Enabled Enabled...
  • Page 30 - Notes - - 30 -...
  • Page 31: Lynx Touch Series Summary Of Connections Diagram

    - 31 -...
  • Page 32 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright © 2014 Honeywell International Inc. www.honeywell.com/security Ê800-199766Š 800-19976 12/14 Rev. B...