Programming the Control
Program the Communications Module (Continued)
SCREEN
City ID
CS ID
Sub ID
Supervision
24 Hours
Old Alarm Time
10 Minutes
Remote Acc. Comm.
Disabled
Multi Mode Comm.
Disabled
IP Fault Time (min)
00
Use DHCP
Yes
NIC IP Address
255.255.255.255
Subnet Mask
255.255.255.255
Gateway IP Address
255.255.255.255
DNS Server IP Address
255.255.255.255
4.
Select "City ID". Enter the 2-digit Primary City ID (Decimal).
Options
01-99
5.
Select "CS ID". Enter the 2-digit Primary Central Station ID (HEX).
Options
01-FE
6.
Select "Sub ID". Enter the 4-digit Subscriber Account Number (Decimal).
Options
0001-9999
7.
Select "Supervision". The system scrolls between the following options:
24 Hours
None
30 Days
8.
Select "Old Alarm Time". The system scrolls between the following options. Use the
down  arrow to scroll to the next page of options.
10 Minutes
15 Minutes
30 Minutes
1 Hour
2 Hours
4 Hours
8 Hours
12 Hours
24 Hours
9.
Select "Remote Acc. Comm". The system toggles between "Disabled" and
"Enabled".
Note: This field will not be programmable unless it is enabled when creating the
Communications Module account in AlarmNet.
10. If "Remote Acc. Comm." was enabled in the previous step, the "Multi Mode Comm."
option is displayed. The system scrolls between the following options.
Disabled
Relay Reports
Enhanced Reports
Note: This field will not be programmable unless it is enabled when creating the
Communications Module account in AlarmNet. The Relay Reports option should
not be selected when using TotalConnect 2.1 Service.
11. Use the down  arrow to scroll to the next page of options. If IP was selected in
step 2, proceed to step 12. If GSM was selected in step 2, proceed to step 19.
12. Select "IP Fault Time (min)". Enter the time delay (in minutes) on the keypad.
Options
00-99
13. Select "Use DHCP". The system toggles between "Yes" and "No". If "No" is selected
the system displays four additional options. If "Yes" is selected, skip to step 18.
14. Select "NIC IP Address". Enter the 4-part address on the displayed keypad.
15. Select "Subnet Mask". Enter the 4-part address on the displayed keypad.
16. Select "Gateway IP Address". Enter the 4-part address on the displayed keypad.
17. Select "DNS Server IP Address". Enter the 4-part address on the displayed keypad.
18. If "IP" was selected in step 2, select "Save" and then select "OK" when the
"Programming Done" screen appears. Proceed to "Diagnostics" section in order to
register the device.