Table 3.3, Battery Type To Charge Voltages - Magnum Energy ME-MR Series Owner's Manual

Inverter remote control
Table of Contents

Advertisement

SETUP: 04 Battery Type - Used to select the battery type, which
determines the battery charge profi le and ensures the batteries are receiving
the proper charge voltage. The fi xed voltage selections are GEL (for Gel
batteries), Flooded (for liquid lead acid batteries), AGM 1 (for Lifeline AGM
batteries) and AGM 2 (for East Penn/Deka/Discover/Trojan AGM batteries);
See Table 3.3 to determine the specifi c charge voltage based on the Battery
Type selected.
Default setting: BattType = Flooded
Info: The voltage settings shown in Table 3.3 are based on the Battery
Temperature Sensor (BTS) being disconnected or at a temperature of
77° F (25° C). If the BTS is connected, the actual charge voltage will
increase if the temperature around the BTS is colder than 77° F (25°
C) and decrease if hotter than 77° F (25° C). This ensures the batteries
receive the correct charge voltage even if they become cold or hot.

Table 3.3, Battery Type to Charge Voltages

Battery
Inverter
Type
Voltage
12 VDC
GEL
24 VDC
48 VDC
12 VDC
Flooded
24 VDC
48 VDC
12 VDC
AGM 1
24 VDC
2
48 VDC
12 VDC
AGM 2
24 VDC
3
48 VDC
Note 1: voltage same as absorption voltage - to prevent equalization.
Note 2: specifi cations for Concord (Lifeline Series) AGM batteries.
Note 3: specifi cations for East Penn, Deka, Discover and Trojan AGM batteries.
Bottom line show s
current "saved" setting
BAT TYPE
M EN U
Flooded
H O M E
If this setting is correct , press
men u button to access
different m enu item s
press
BAT TYPE
.......
Gel
Figure 3-4, SETUP: 04 Battery Type Selections
©2009 Magnum Energy Inc.
Absorption
Voltage
14.1 VDC
13.6 VDC
28.2 VDC
27.2 VDC
56.4 VDC
54.4 VDC
14.6 VDC
13.4 VDC
29.2 VDC
26.8 VDC
58.4 VDC
53.6 VDC
14.3 VDC
13.1 VDC
28.6 VDC
26.2 VDC
57.2 VDC
52.4 VDC
14.5 VDC
13.5 VDC
29.0 VDC
27.0 VDC
58.0 VDC
54.0 VDC
If a different setting is
required:
O N / O F F
C H A N G E
press
BAT TYPE
BAT TYPE
.......
Flooded
AGM 1
Setup
Float
Equalization
Voltage
Voltage
14.1 VDC
28.2 VDC
56.4 VDC
15.5 VDC
31.0 VDC
62.0 VDC
15.5 VDC
31.0 VDC
62.0 VDC
14.5 VDC
29.0 VDC
58.0 VDC
T o save the current
setting displayed :
SA VE
H O L D
press
BAT TYPE
.......
AGM 2
1
1
1
1
1
1
11