1: Disable - Fire-Lite MS-9200(C) Instruction Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200(C):
Table of Contents

Advertisement

Program Change - Level 2
Enter the Level 2 password (default = 11111) then press the ENTER key to access Programming Change Level 2.
The screen shown below will appear:
From this screen, the available function choices include point Disable, Clear History, Walktest, Set Time and Check
programming.
3.4.1 Disable
Pressing '1' displays the following screen:
Press the * key to display detectors, the # key to display modules, followed by the device address, then the ENTER
key. A typical display is shown below:
A point is then displayed on the screen similar to a Point Edit display but with the current status label (ENABLE)
blinking. The current status label may show: NORMAL, TROUBL, DISABL, ALARM, ACTIVE, PROGRM, TEST
01, ON, OFF. The status label can be changed to DISABL or back to its present status by pressing the up or down
arrow keys. The disable status is entered/stored in memory by pressing ENTER. The display then returns to the DIS-
ABLE/ENABLE screen shown above. The operator may then enter a new point number, or may press up/down to
bring up the next lower/higher address point. The disabling of initiating devices that are in alarm or control points
that are ON occurs after the RESET key is pressed.
All disabled points will scroll on the LCD display and the system will remain in trouble until all programmed points
are enabled.
48
1=DISABL 2=CLR HIST
3=WALK 4=TIME 5=CHEK
DISABLE/ENABLE
PRESS */#,AA,ENTER
ENABLE
SMOKE DET P01
NORTH BASEMENT
Document #51003
Z01
Rev.E
01/11/02
P/N 51003:E