Disable Point - Fire-Lite MS-9050UDC User Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9050UDC:
Table of Contents

Advertisement

3.7.1 Disable Point

Pressing 1 for Point Program, while viewing Maintenance Screen #1 will cause the following
screens to be displayed:
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Maintenance Screen #1
Select the device type by pressing 1 for an addressable detector or 2 for an addressable module.
The operator will be prompted to enter the three digit device address as shown in the following
example for a detector:
A flashing cursor will appear in the bottom left corner of the display, prompting for the three digit
device address. When the third digit is enter, 001 for example, a screen will appear which will
allow enabling or disabling of the selected point, as illustrated in the following example:
Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled No.
MS-9050UD Series PN 52413:D 12/15/08
POINT PROGRAM
1=DETECTOR
2=MODULE
Device Select Screen
EDIT DETECTOR
ENTER POINT ADDRESS
***
Address Select Screen
EDIT DETECTOR 1D001
1=ENABLED
Enable/Disable Select Screen
Programming
YES
139

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9050udMs-9050ude

Table of Contents