Example) By using the Mollier diagram of R-22, find the compression ratio, refrigeratiny effect, work of compres-
sion, calorie of condensation, circulation amount of refrigerant, coefficient of performance, and refriger-
ating effect per 1KW.
Condensation pressure : Pd = 18.1kg/cm
Evaporation pressure
Compression ratio
Enthalpy
Accordingly, Refrigerating effect
Work of compression
Calorie of condensation
Circulation amount of refrigerant : G=Q/q
COP
Refrigerating effect per 1KW
TCL Air Conditioner Service Manual
abs
2
: Ps = 6.5kg/cm
abs
2
: Pr = Pc/Pe = 18.1/6.5 = 2.78
: i
= 148.5kcal/kg
A
i
= 158.5kcal/kg
B
i
= 110kcal/kg
C
i
= 110kcal/kg
D
i
= i
= 112kcal/kg
C'
D'
i
= 148kcal/kg
E
: q
1
: A
: q
2
: q
1
: k = 860 x 3.85 = 3311 [kcal/h. KW]
15.0
40°C
3.0
= i
- i
= 148.5 - 110 = 38.5 [kcal/kg]
A
D
= i
- i
= 158.5 - 148.5 = 10 [kcal/kg]
1
B
A
= i
- i
= 158.5 - 110 = 48.5 [kcal/kg]
B
C
= 3320/38.5 = 86.2 [kg/h.RT] (per 1 Refrigerating Ton)
1
/A
= 38.5/10 = 3.85
1
14
46°C
C
38°C
C'
8°C
E
16°C
D
D'
A
110 112
148 148.5 158.5
3
0.0016m /kg
B
75°C
3
0.0024m /kg

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TAC-07CS and is the answer not in the manual?

Questions and answers

JAVIER
April 4, 2025

Cual es la conexión de la entrada de corriente de split tcl

1 comments:
Mr. Anderson
April 4, 2025

The power input connection for the TCL TAC-07CS split air conditioner is as follows:

- For the indoor unit: Connect terminals 1 (WHITE), 2 (BLUE), and 3 (BROWN) to the corresponding terminals on the outdoor unit.
- The power supply connects to terminals L (BROWN) and N (BLUE) on the indoor unit.
- A GREEN/YELLOW wire is used for grounding.
- A 25A circuit breaker or time delay fuse should be installed between the main power source and the unit if a power plug is not used.