TCL Air Conditioner Service Manual Part Ⅰ Technical Information 1. Important Notice This service manual is intended for use by individuals possessing adequate backgrounds of electrical, electronic and mechanical experience. Any attempt to repair the appliance may result in personal injury and property damage.
TCL Air Conditioner Service Manual 3.2 PCB LAOUT (Only for reference) Indoor unit A010268 9 10 Transformer IN ODU AC power output Transformer OUT Fuse ODU AC power input AC fan motor driving IDU/ODU wiring connection --N connector Power supply --N connector...
Page 8
TCL Air Conditioner Service Manual A010403 A010412 ...
Page 9
TCL Air Conditioner Service Manual A010283 Outdoor unit 9K, 12K A010313 Mainly relay Fuse L, N & 1 (communication) wiring 4-way valve Heater motor connector Electronic expansion valve Discharge sensor connector OAT/OPT sensor connector LED5 ...
Page 10
TCL Air Conditioner Service Manual A010386 18,24K A010286 DRED(OPTION) OAT/OPT connector Discharge sensor connector Electronic expansion valve AC/DC motor connector Heater 4-way valve LED5 Communication wiring Fuse L , N line Mainly relay LED1-LED4 Note: OAT: Outdoor Ambient Temperature OPT: Outdoor pipe temperature ...
TCL Air Conditioner Service Manual 4. Electronic Controller Introduction 4.1 Electronic Controller RT-------Room Temperature. IPT------Indoor Pipe (Coil) Temperature. ST------Indoor Setting Temperature. OPT---Outdoor Pipe Temperature. OAT---Outdoor Ambient Temperature. ODT---Outdoor Discharge Temperature. CRT---Compensated Room Temperature. IDU--- Indoor unit ODU---Outdoor unit.
Page 12
TCL Air Conditioner Service Manual 5. Anti-frosting protection Control the unit operation frequency and the frequency changing rate to achieve anti-frosting protection. 1). Frequency Slowly Increasing(FSI): a. If 6℃≤IPT<7 ℃ , the frequency increasing rate is 1Hz/60s, slowly increasing operation speed.
Page 13
TCL Air Conditioner Service Manual 6). In the process of unit operation, once the compressor ceased, it should be 3 min delay for the next procedure. 3. IDU time delay: When compressor stops or unit switches off while in heating mode, IDU fan motor will work for a few seconds more to prevent overheat.
Page 14
TCL Air Conditioner Service Manual COMPRESSOR 4-way VALVE OUTDOOR FAN Defrosting max time Defrosting end off: Compressor stops working, and re-starts to working after 50s delay; 7. Cold air prevention: This function intends to prevent cold air from being discharged when the heating operation starts up 1). IDU fan motor cold air prevention .When RT<24℃: a. If ITP>31℃ while compressor works for 5 min, fan motor will work according to preset fan speed. b. If IPT≤31℃, fan motor stops working while compressor operation within 2min, if IPT≥27℃, fan motor works in low speed 2 min, then change to preset speed. When RT≥24℃: ...
Page 15
TCL Air Conditioner Service Manual 4). Set other function as MODE, FAN SPEED, SWING etc. 5). Press TIMER ONCE AGAIN to confirm the TIME ON setting TIMER OFF 1). TIMER OFF can be set only when the air conditioner is ON.
Page 16
TCL Air Conditioner Service Manual The failure and times for protection will eliminate immediately once the unit to be switched off, on fan mode or changed to be heating mode from others. Note: If the defective failure can’t be recovered, the failure can’t eliminate even if operation mode changed.
Page 17
TCL Air Conditioner Service Manual code as IDU/ODU communication failure. Once the IDU & ODU communication recovery, and also the compressor stopped for 3 min already, can the unit be recovered to operate. ...
TCL Air Conditioner Service Manual PART Ⅱ Installation and Maintenance 1. Notes for installation and maintenance Safety Precautions Important! Please read the safety of precautions carefully before installation and maintenance. The following contents are very important for installation and maintenance. Please follow the instructions bellow.
Page 19
TCL Air Conditioner Service Manual Improper installation may lead to fire hazard, explosion, electric shock or injury. Safety precautions for Installing and Relocating the unit. To ensure safety, please be mindful of the following precautions. Warnings When installing or relocating the unit, be sure to keep the refrigerant circuit free from air or substances other than the specified refrigerant.
Page 20
TCL Air Conditioner Service Manual Introduction R32, R290 air conditioner installation 1) Introduction to Refrigerants R32 & R290 The refrigerants used for air conditioners are environmentally friendly hydrocarbons R32 and R290. The two kinds of refrigerants are combustible and odorless. Moreover, they can burn and explode under certain condition.
Page 21
TCL Air Conditioner Service Manual Caution: Please contact the nearest after-sale service center when maintenance is necessary. At the time of maintenance, the maintenance personnel must strictly comply with the Operation Manual provided by the corresponding manufacturer and any non-professional is prohibited to maintain the air conditioner.
Page 22
TCL Air Conditioner Service Manual station and it is prohibited to weld the refrigerant pipe or conduct other operations on the user’s site. It is necessary to choose the place where the inlet and outlet air of the indoor unit is even.
Page 23
TCL Air Conditioner Service Manual professional equipment recommended by the air conditioner manufacturer. Check the refrigerant leak detector whether has been calibrated. The set maximum alarm concentration of the refrigerant leak detector should not exceed 25% of the lower explosion limit (LEL), the refrigerant leak detector must be working during maintenance.
Page 24
TCL Air Conditioner Service Manual The main power switch should be set outside the maintenance location and equipped with protective (explosion-proof) devices. It is necessary to provide firefighting devices such as dry powder or carbon dioxide fire extinguisher appropriate for extinguishing the electrical fire and keep such firefighting devices in a usable condition.
Page 25
TCL Air Conditioner Service Manual A maintenance station should establish emergency handling plans. It is necessary to take appropriate precautionary measures in work. For example, it is prohibited to enter the location with any kindling material and it is prohibited to wear clothing or shoes which easily produce static.
TCL Air Conditioner Service Manual 2 Installation 2.1 Installation Dimension Diagram Space to the wall At least 15cm At least 15cm Space to the wall Space to the obstruction Space to the floor Space to the obstruction Drainage pipe Connecting wire ...
TCL Air Conditioner Service Manual 1) Must follow the electric safety regulations when 2.4 Position installing the unit. Indoor unit 2) According to the local safety regulations, use Install the indoor unit level on a strong wall that is qualified power supply circuit and air switch.
Page 29
TCL Air Conditioner Service Manual 9K(770X) The hole must slope downwards towards the exterior. Note: Keep the drain pipe down towards the direction of the wall hole, otherwise leakage may occur. 1.6.3 Electrical connections---Indoor unit 1).Lift the front panel.
Page 30
TCL Air Conditioner Service Manual Wrap the insulation material around the connecting portion. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
TCL Air Conditioner Service Manual through the drain pipe. the drain pipe. 1) Fasten the drain port in the 25mm hole placed in the part of the unit as shown in the picture. 2) Connect the drain port and the drain pipe.
TCL Air Conditioner Service Manual 2.8 Vacuum and gas leakage test 2.9 Final test 1. Use vacuum Pump 1 Preparation of test operation. 1) Air and humidity left inside the refrigerant circuit can The client approves the air conditioner cause compressor malfunction.
TCL Air Conditioner Service Manual 3. Maintenance 3.1 Failure code Code Reason Remark IDU & ODU Communication failure The IDU & ODU wiring connection correct? IDU Room Temperature sensor failure.(IDU IDU sensor and PCB. RT failure) IDU Coil temperature sensor failure.(IDU IPT IDU sensor and PCB.
Page 34
TCL Air Conditioner Service Manual Cooling system gas flow abnormal Please check the troubleshooting for detail. PROTECTION. PFC PROTECTION Please check the troubleshooting for detail. The Compressor lack of phase / Anti-phase Please check the troubleshooting for detail.
TCL Air Conditioner Service Manual 3.2 Trouble shooting 3.2.1 E0 ---IDU & ODU communication failure Start Display E0 IDU wiring Check and E0 disappear? connection correct ? re-connect Check communication, Replace/ E0 disappear? earth wiring and the re-connect connection, in good condition? ODU wiring ...
Page 36
TCL Air Conditioner Service Manual 3.2.2 E1, E2 ---IDU Room temperature sensor and/or coil temperature sensor failure. Start Display E1or E2 Is the sensor well Re-connect connected to PCB E1/E2 disappear? Multi-meter check the Replace the sensor sensor, is it open or...
Page 37
TCL Air Conditioner Service Manual 3.2.3 E4 --- AC Cooling system abnormal (Gas not enough) Start Display E4 Check the pressure AC pressure correct? Check the sensor short or (cooling:0.8-1.3Mpa,/ open? heating 2.0-3.6Mpa) Replace the sensor Check the valves open or...
Page 38
TCL Air Conditioner Service Manual 3.2.4 E6----IDU ventilation failure (PG and DC fan motor only) Start Display E6 Turn the fan blades by hand while power-off Adjust the motor and blade Can the fan blades run assembly so that rotor can smoothly? run smoothly.
Page 39
TCL Air Conditioner Service Manual 3.2.5 E3, E7 or E8----ODU Coil temperature sensor, Ambient temperature sensor or Discharge temperature sensor failure. When any of the sensor resistance open or short circuit , unit will display failure code as E3/E7 or E8, IDU and ODU turns off.
Page 40
TCL Air Conditioner Service Manual 3.2.6 E9---ODU IPM /Compressor drive fault If unit have 6 times stopping works for IPM protection (P0) continuously, it will display E9 error, and unit can’t be recovered to operation, except press ON/OFF button.
Page 41
TCL Air Conditioner Service Manual 3.2.7 EF---ODU DC fan motor failure Shut off Check the fan blade by Re install the DC motor hand, can it rotate freely Works normal? Fan motor well Re-connect connect to PCB Works normal? 1.
Page 42
TCL Air Conditioner Service Manual 3.2.8 EU---ODU voltage test sensor failure After power relay works, when tested voltage effective value less than 50V for 3s continuously, unit will display EU. Start Display EU Test voltage btw ODU Check while voltage...
Page 43
TCL Air Conditioner Service Manual 3.2.9 P0---IPM protection When overheat or overcurrent for IPM, AC unit will display P0protection. Display P0 Restart unit. It works normal? Wiring connection Re-connect U/V/W correct? P0 disappear? ODU fan motor no Replace ODU...
Page 44
TCL Air Conditioner Service Manual 3.2.10 P1--- Over / under voltage protection 1. Test voltage between L &N, When the power supply V>AC260V or V<AC150V, AC will display P1 protection, unit will recover back to previous status while V>AC155V.
Page 45
TCL Air Conditioner Service Manual 3.2.11 P2---Over Current protection When the AC unit running current more than I , it will stop and display P2 protection. Note: for different AC model, I has difference valve. Display P2 ODU fan motor...
Page 46
TCL Air Conditioner Service Manual 3.2.12 P4 ---ODU Discharge temperature overheating protection Display P4 ODU temperature Normal protection higher than 60 ℃? ODU location Adjust ODU Enough space for Unit operate? acceptable? installation ventilation? Condenser too Clean IDU filter or...
Page 47
TCL Air Conditioner Service Manual 3.2.13 P5---Sub-cooling protection on Cooling/Dry mode On Cooling or Dry mode, when IDU evaporator coil temperature IPT<1℃ continuously for 3 min after compressor start up for 6 min, CPU will switch off outdoor unit and show P5 failure code.
Page 48
TCL Air Conditioner Service Manual 3.2.14 P6---Overheating protection on Cooling mode On Cooling or Dry mode, when ODU condenser coil temperature OPT≥62℃ , MCU will switch off outdoor unit and show P6 failure code. Display P6 ODU fan motor...
Page 49
TCL Air Conditioner Service Manual 3.2.15 P7---Overheating protection on Cooling mode On heating mode, when IDU evaporator coil temperature IPT≥62 ℃ , ODU PCB will switch off outdoor unit and show P7 failure code. Display P7 ODU fan motor...
Page 50
TCL Air Conditioner Service Manual 3.2.16 P8---Outdoor Overtemperature/Under-temperature protection When environment temperature as below condition, the compressor will stop working, after 200s delay, the IDU will show P8 failure code. (1). On Cooling or Dry mode: ODU ambient temperature: OAT<-20℃ or OAT>63℃;...
Page 51
TCL Air Conditioner Service Manual 3.2.17 P9---The compressor driving protection (the compressor load abnormal) When compressor start up or in the process of operation, if: (1). MCU can’t test the feedback signal from compressor, or (2). Tested a abnormal signal from compressor, or (3).
Page 52
TCL Air Conditioner Service Manual 3.2.18 F4---Cooling system Gas flow abnormal protection When compressor startup, unit will check the variation of IDU coil temperature. If there is mistake installer forgetting to open the 2-way or 3-way valve on ODU, the gas can’t flow in the cooling system, it will show F4 protection.
Page 53
TCL Air Conditioner Service Manual 3.2.19 F5---PFC Protection PFC Overcurrent protection F5 Code Check the power supply, Display F5 by is it abnormal? (this is random? normal protection) Display F5 frequently Switch off the unit for 3 Still F5?
Page 54
TCL Air Conditioner Service Manual 3.2.20 F6 The Compressor Lack of phase / Anti-phase protection. If ODU PCB can’t test one, or even three phase of compressor current, it will show F6 protection. Display F6 Check compressor Re-connect...
Page 55
TCL Air Conditioner Service Manual 3.2.21 F7---Module temperature protection. IPM overtemperature protection, when IPM temperature more than 95℃, it will show F7. Display F7 Clean or adjust the gap IPM well contact to Any dust or gap btw...
Page 56
TCL Air Conditioner Service Manual 3.2.22 F8---4-Way Value Reversing abnormal On heating mode, if IDU Coil temperature tested lower than Room temperature 5℃ or even more after compressor works for 8min, unit will show F8 code. Display F8...
Page 57
TCL Air Conditioner Service Manual 9.2.23 Fy--- Gas leakage protection After compressor works in high frequency for 9 min, if the temperature on IDU evaporator & ODU condenser has only a little variation comparing previous, but, the compressor discharge temperature on high level, then the unit will show Fy failure code.
TCL Air Conditioner Service Manual 4. Disassembly IDU & ODU 4.1. IDU Disassembly Steps Reference photo 1. Before disassembly The orginal status. 2. Disassembly front panel, display board and WIFI module. 显示盒 Display box A. Open front panel. B. Remove one screw and take the displa box out from the panel. C. Release panel axis which shown in re arrows out from middle frame and tak the panel out. D. Unscrew and take the WIFI module ou from middle frame. ...
Page 59
TCL Air Conditioner Service Manual 4. Remove the electric control box cover Unfix one screw on the cover of 固 electric box, and remove the cover. 定 The 螺 Fix screw 钉 5. Remove the filter Push the filter upwards a little, you can take it out from unit. 6. Disassembly the middle frame. Clasps 插扣 A. Open the screw cover, and unfix ...
Page 60
TCL Air Conditioner Service Manual 7. Disassembly the electric control box. 电控盒 Electric control box A. Remove the RT & IPT out from evaporator; B. Unscrew all the earth ground wirings on the evaporator. C. Take all the connectors out from PCB. D. Unfix one screw of the control box ...
Page 61
TCL Air Conditioner Service Manual 9. Disassembly the evaporator screws Screws + motor 螺钉/卡扣 螺钉 A. Unfix 2 screws of left side shown as cover picture. B. Unfix 2 screws of right side on motor cover/right support plate. C. Take the evaporator out from unit by uplifting the IUPUT/OUTPUT pipes slightly. 10. Remove the MOTOR COVER 螺钉 screws Unfix 4 screws on the motor cover with base frame. ...
TCL Air Conditioner Service Manual 4.2 ODU Assembly Step Reference picture step1:Remove the PCB Cover , valve Cover and top cover 1). Unfix one screw on the PCB cover, you can take the cover out from unit. 2). Unfix one screw...
Page 63
TCL Air Conditioner Service Manual ODU middle separate plate and base plate, uplift front panel you can take it out from unit. step3:Disassemble the Left and Right plate. Unfix screws btw Right Plate and the Electric Box assembly, Valve...
Page 64
TCL Air Conditioner Service Manual step4:Disassemble the Axis Fan Blade Unscrew the fan blade nut, and take the blade out. step5:Disassemble the electric box Unfix screw btw Electric Box and motor supporter etc. loosen the wiring clamp, then you can take the control box out.
Page 65
TCL Air Conditioner Service Manual Shown as picture to take the cotton out step7:Disassemble the separate plate Unfix the screw btw separate plate and unit, and take it out step8:Disassemble the 2 and 3-way valve ...
Page 66
TCL Air Conditioner Service Manual Unfix screw btw Valve plate and base, you can take the 2-way and 3-way valve out by welding. Note: 1). The welding can only place while no gas in the unit. 2). Pay attention to the fire to prevent any injury.
Page 67
TCL Air Conditioner Service Manual step11:Remove the fan motor and fan supporter. Unfix screws btw fan motor with supporter, and supporter with base plate. Note: Pay attention to the motor wiring, it can’t be taken out by force.
TCL Air Conditioner Service Manual Appendix 3 Pipes Flaring Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure. A. Cut the pipes and the cable. 1) Use the piping kit accessory or the pipes purchased locally.
TCL Air Conditioner Service Manual Appendix 4 THERMISTOR TEMPERATURE CHARACTERISTICS 1). Indoor unit and outdoor exchange temperature and outside air temperature sensor temperature characteristics TEMP. Resistance Voltage of TEMP. Resistance Voltage of TEMP. Resistance Voltage of ℃ ℃...
Page 71
TCL Air Conditioner Service Manual TH1: indoor room temperature sensor and outside air temperature sensor TH2: indoor exchange temperature sensor and outside exchange temperature sensor Before measuring resistance, disconnect connectors as shown above. Outdoor unit sensor temperature characteristics TEMP.