TCL Air Conditioner Service Manual Part Ⅰ Technical Information 1. Important Notice This service manual is intended for use by individuals possessing adequate backgrounds of electrical, electronic and mechanical experience. Any attempt to repair the appliance may result in personal injury and property damage.
TCL Air Conditioner Service Manual 3.2 PCB LAOUT(Only for reference) Indoor unit Indoor PCB 7k, 9K, 12K, 18K A010268 9 10 ODU AC power output Fuse Transformer out IDU AC power input AC motor driver IDU/ODU wiring connection-N connector Power supply-N connector...
Page 9
TCL Air Conditioner Service Manual 7K, 9K, 12K, 18K Top view A010235 1 ODU AC power output 2 Fuse 3 ODU AC power input 4 AC motor driver IDU/ODU wiring connection‐N 5 connector 6 Power supply‐N connector 7 Left‐Right swing connector 8 Up‐Down swing connector 9 AC Motor feedback Display Emergency button Temperature sensor connector Trans former IN Trans former OUT Anion connrctor 7K, 9K, 12K, 18K,24K...
Page 10
TCL Air Conditioner Service Manual 7K, 9K, 12K, 18K,24K Top view A010422 1 Trans former IN 2 ODU AC power output 3 Fuse 4 ODU AC power input 5 AC motor driver IDU/ODU wiring 6 connection‐N connector Power supply‐N 7 connector Left‐Right swing 8 connector Up‐Down swing 9 connector 10 AC Motor feedback 11 Emergency button Temperature sensor 12 ...
TCL Air Conditioner Service Manual 4. Electronic Controller Introduction 4.1 Electronic controller RT-------Room Temperature. IPT------Indoor Pipe (Coil) Temperature. ST------Indoor Setting Temperature. OPT--- Outdoor Pipe Temperature. CRT--- Compensated Room Temperature. IDU--- Indoor unit ODU--- Outdoor unit. Note: When AC finishing installation, because of the air ventilation and the distance of temperature test sensor to different location of the house, the temperature for IDU PCB control need compensation.
Page 12
TCL Air Conditioner Service Manual 2). When switch on unit on cooling mode, ODU fan motor will delay 5s after compressor starts up. 4.1.2.4. When ODU failure or stops for protection, IDU works as preset. 4.1.2.5. Anti-frosting protection While condition a), b) matched, the AC unit transferred to anti-frosting protection.
Page 13
TCL Air Conditioner Service Manual c. changed to fan mode. 4). Under normal operation, the compressor can be stopped by program until it works for 6 min at least once starts 5). In the process of unit operation, once the compressor ceased, it should be 3 min delay for the next procedure.
Page 14
TCL Air Conditioner Service Manual 2). Vane blade operation for cold air prevention. a. If the vane works on status of non-swing: While IPT increase to a special degree, the vane blade will change the position to: ① Default angle; or ②...
Page 15
TCL Air Conditioner Service Manual 4.1.8 Emergency switch When the EMERGENCY switch is pressed one time, COOLING mode is selected and if it pressed again within 3s, HEATING mode selected, while press once again, the unit will be switched off.
TCL Air Conditioner Service Manual PART Ⅱ Installation and Maintenance 1. Notes for installation and maintenance Safety Precautions Important! Please read the safety of precautions carefully before installation and maintenance. The following contents are very important for installation and maintenance. Please follow the instructions bellow.
Page 17
TCL Air Conditioner Service Manual 6) Make sure no foreign objects are left in the unit after finishing installation. Improper installation may lead to fire hazard, explosion, electric shock or injury. Safety precautions for Installing and Relocating the unit.
Page 18
TCL Air Conditioner Service Manual install your air conditioner in a room with an appropriate area and use it correctly. Compared with ordinary refrigerants, Refrigerants R32 & R290 are environmentally friendly and do not destroy the ozone sphere and that their values of greenhouse effect are also very low.
Page 19
TCL Air Conditioner Service Manual Caution: Please contact the nearest after-sale service center when maintenance is necessary. At the time of maintenance, the maintenance personnel must strictly comply with the Operation Manual provided by the corresponding manufacturer and any non-professional is prohibited to maintain the air conditioner.
Page 20
TCL Air Conditioner Service Manual user’s site. It is necessary to choose the place where the inlet and outlet air of the indoor unit is even. It is necessary to avoid the places where there are other electrical products, power switch plugs and sockets, kitchen cabinet, bed, sofa and other valuables right under the lines on two sides of the indoor unit.
Page 21
TCL Air Conditioner Service Manual Check the maintenance equipment is applicable to the refrigerant or not and it is only allowed to use the professional equipment recommended by the air conditioner manufacturer. Check the refrigerant leak detector whether has been calibrated. The set maximum alarm concentration of the refrigerant leak detector should not exceed 25% of the lower explosion limit (LEL), the refrigerant leak detector must be working during maintenance.
Page 22
TCL Air Conditioner Service Manual and have a leak detecting instrument management system. It is necessary to confirm that the leak detector can work normally before maintenance. The main power switch should be set outside the maintenance location and equipped with protective (explosion-proof) devices.
Page 23
TCL Air Conditioner Service Manual Before doing the trial operation after finishing the maintenance, it is a must to use a practical leak detector to inspect the leakage and reliability of ground connection in order to ensure that no refrigerant leakage and reliable ground connection.
TCL Air Conditioner Service Manual 2 Installation 2.1 Installation Dimension Diagram Space to the wall At least 15cm At least 15cm Space to the wall Space to the obstruction Space to the floor Space to the obstruction Drainage pipe Connecting wire ...
TCL Air Conditioner Service Manual 2.4 Electricity and wiring 2.3 Position Safety precaution Indoor unit 1) Must follow the electric safety regulations when Install the indoor unit level on a strong wall that installing the unit. is not subject to vibrations 2)...
Page 27
TCL Air Conditioner Service Manual 7K/9K(698X) The hole must slope downwards towards the exterior. Note: Keep the drain pipe down towards the direction of the wall hole, otherwise leakage may occur. 2.5.3 Electrical connections---Indoor unit 1).Lift the front panel.
Page 28
TCL Air Conditioner Service Manual Wrap the insulation material around the connecting portion. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
TCL Air Conditioner Service Manual Pay attention that water is drained in a suitable place. Insert the pipe connection into the relative slot. Press to join the pipe connection to the base. Electronic connections 1. Take the cover away.
TCL Air Conditioner Service Manual 2.7 Vacuum and gas leakage test 2.8 Final test 1. Use vacuum Pump 1 Preparation of test operation. 1) Air and humidity left inside the refrigerant circuit The client approves the air conditioner can cause compressor malfunction.
TCL Air Conditioner Service Manual 3. Maintenance 3.1 Failure code Code Reason Remark IDU Room Temperature sensor failure. IDU sensor and PCB. (IDU RT failure) IDU Coil temperature sensor failure.(IDU IDU sensor and PCB. IPT failure) Gas not enough...
TCL Air Conditioner Service Manual 3.2 Trouble shooting 3.2.1 E1, E2 ---IDU Room temperature sensor and/or coil temperature sensor failure. Start Display E1or E2 Is the sensor well Re-connect connected to PCB E1/E2 disappear? Multi-meter check the Replace the sensor...
Page 33
TCL Air Conditioner Service Manual 3.2.2 E6----IDU ventilation failure (PG and DC fan motor only) Start Display E6 Turn the fan blades by hand while power-off Adjust the motor and blade Can the fan blades run assembly so that rotor can smoothly? run smoothly.
Page 34
TCL Air Conditioner Service Manual 3.2.3 P7---Overheating protection on Cooling mode On heating mode, when IDU evaporator coil temperature IPT≥62 ℃ , ODU PCB will switch off outdoor unit and show P7 failure code. Display P7 ODU fan motor...
TCL Air Conditioner Service Manual 4. Disassembly IDU & ODU 4.1. IDU Disassembly Steps Reference photo 1. Before disassembly The orginal status. 2. Disassembly front panel, display board and WIFI module. 显示盒 Display box A. Open front panel. B. Remove one screw and take the displa box out from the panel. C. Release panel axis which shown in re arrows out from middle frame and tak the panel out. D. Unscrew and take the WIFI module ou from middle frame. WiFi模块...
Page 36
TCL Air Conditioner Service Manual 4. Remove the electric control box cover Unfix one screw on the cover of 固 定 The electric box, and remove the cover. Fix 螺 screw 钉 5. Remove the filter Push the filter upwards a little, you can take it out from unit. 6. Disassembly the middle frame. Clasps 插扣 A. Open the screw cover, and unfix ...
Page 37
TCL Air Conditioner Service Manual 7. Disassembly the electric control box. 电控盒 Electric control box A. Remove the RT & IPT out from evaporator; B. Unscrew all the earth ground wirings on the evaporator. C. Take all the connectors out from PCB. D. Unfix one screw of the control box ...
Page 38
TCL Air Conditioner Service Manual 9. Disassembly the evaporator screws Screws + motor 螺钉/卡扣 螺钉 A. Unfix 2 screws of left side shown as cover picture. B. Unfix 2 screws of right side on motor cover/right support plate. C. Take the evaporator out from unit by uplifting the IUPUT/OUTPUT pipes slightly. 10. Remove the MOTOR COVER 螺钉 screws Unfix 4 screws on the motor cover with base frame. 11. Disassembly fan motor and fan blade. ...
TCL Air Conditioner Service Manual 4.2 ODU Assembly Step Reference picture Before disassembly 1:Remove the PCB Cover , Valve Cover and Top Cover 1). Unfix one screw on the PCB cover, you can take the cover out from unit.
Page 40
TCL Air Conditioner Service Manual Unfix screws btw the top cover with front panel, left and right plate, then you can take the top cover out. 2:Disassemble the Fan Guard and Front Panel 1). Unfix screw btw fan guard and front panel, and take the fan guard out.
Page 41
TCL Air Conditioner Service Manual 3:Disassemble the Left and Right side Plate. Unfix screws btw Right Plate and the Electric Box assembly, Valve Plate , Base Plate, then you can take the Right plate out. Unfix screws btw left...
Page 42
TCL Air Conditioner Service Manual 5:Disassemble the Electric Box Unfix screw btw Electric Box and motor supporter etc. loosen the wiring clamp, then you can take the control box out. 6:Take out the Noise Cotton Shown as picture to take the cotton out.
Page 43
TCL Air Conditioner Service Manual Unfix the screw btw separate plate and unit, and take it out. 8:Disassemble the 2 and 3-way Valve Unfix screw btw Valve plate and base, you can take the 2-way and 3-way valve out by welding.
TCL Air Conditioner Service Manual Unscrew the nuts and take the compressor out. 11:Remove the Fan Motor and motor Supporter. Unfix screws btw fan motor with supporter, and supporter with base plate. Note: Pay attention to the motor wiring, it can’t be taken out by force.
TCL Air Conditioner Service Manual Appendix 2 The Pipe length and Gas charging Indoor unit Outdoor unit Pipe l ength is Pi pe length is 15 meters Max. 15 meters Max. Indoor unit Outdoor unit Refrigerant piping Additional refrigerant Max.
TCL Air Conditioner Service Manual Appendix 3 Pipes Flaring Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure. A. Cut the pipes and the cable. 1) Use the piping kit accessory or the pipes purchased locally.
TCL Air Conditioner Service Manual Appendix 4 THERMISTOR TEMPERATURE CHARACTERISTICS 1). Indoor unit and outdoor exchange temperature and outside air temperature sensor temperature characteristics TEMP. Resistance Voltage of TEMP. Resistance Voltage of TEMP. Resistance Voltage of (℃) (k Ohm) resistance (℃)
Page 48
TCL Air Conditioner Service Manual Resistance at 25℃: 5 kΩ. TH1: indoor room temperature sensor and outside air temperature sensor TH2: indoor exchange temperature sensor and outside exchange temperature sensor Before measuring resistance, disconnect connectors as shown above. ...