Useful functions

4.26.2 Display of the life of the inverter parts (Pr. 255 to Pr. 259)

Degrees of deterioration of main circuit capacitor, control circuit capacitor, cooling fan and inrush current limit
Pr.253
circuit can be diagnosed by monitor.
page 277
When any part has approached the end of its life, an alarm can be output by self diagnosis to prevent a fault.
Pr.261
page 257
(Use the life check of this function as a guideline since the life except the main circuit capacitor is calculated
theoretically.)
For the life check of the main circuit capacitor, the alarm signal (Y90) will not be output if a measuring method of
(4) is not performed.
Parameter
Number
255
Life alarm status display
Inrush current limit circuit
256
life display
Control circuit capacitor life
257
display
Main circuit capacitor life
258
display
Main circuit capacitor life
259
measuring
(1) Life alarm display and signal output (Y90 signal, Pr. 255)
⋅ Whether any of the control circuit capacitor, main circuit capacitor, cooling fan and inrush current limit circuit has
reached the life alarm output level or not can be checked by Pr. 255 Life alarm status display and life alarm signal (Y90).
bit
15
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
Pr. 255
(decimal)
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
366
Name
Initial Value
7
0
1
bit0 Control circuit capacitor life
bit1 Main circuit capacitor life
bit2 Cooling fan life
bit3 Inrush current limit circuit life
Inrush
Bit
Current Limit
(binary)
Circuit Life
1111
1110
1101
1100
1011
1010
1001
1000
×
0111
×
0110
×
0101
×
0100
×
0011
×
0010
×
0001
×
0000
Setting Range
0
(0 to 15)
100%
(0 to 100%)
100%
(0 to 100%)
100%
(0 to 100%)
0, 1
0
(2, 3, 8, 9)
Cooling
Main Circuit
Fan Life
Capacitor Life
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
: With warnings, ×: Without warnings
Description
Display whether the control circuit capacitor,
main circuit capacitor, cooling fan, and each
parts of the inrush current limit circuit has
reached the life alarm output level or not.
Reading only
Display the deterioration degree of the inrush
current limit circuit. Reading only
Display the deterioration degree of the control
circuit capacitor. Reading only
Display the deterioration degree of the main
circuit capacitor. Reading only
The value measured by Pr. 259 is displayed.
Setting "1" and switching the power supply off
starts the measurement of the main circuit
capacitor life.
When the Pr. 259 value is "3" after powering on
again, the measuring is completed. Read the
deterioration degree in Pr. 258.
• Pr.255 setting read
• Pr.255 read
Bit image is displayed
in decimal
Control Circuit
Capacitor Life
×
×
×
×
×
×
×
×