Commercial Power Supply-Inverter Switchover Function (Pr. 57, Pr. 58, Pr. 135 To Pr. 139, Pr. 159) - Mitsubishi Electric FR-A720-0.4K Instruction Manual

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

4.25.2 Commercial power supply-inverter switchover function (Pr. 57, Pr. 58, Pr. 135 to
Pr. 139, Pr. 159)
The complicated sequence circuit for commercial power supply-inverter switchover is built in the inverter. Hence,
merely inputting the start, stop or automatic switchover selection signal facilitates the interlock operation of the
switchover magnetic contactor.
Parameter
Name
Number
57
Restart coasting time
58
Restart cushion time
Electronic bypass
135
sequence selection
MC switchover interlock
136
time
137
Start waiting time
Bypass selection at an
138
alarm
Automatic switchover
139
frequency from inverter
to bypass operation
Automatic switchover
frequency range from
159
bypass to inverter
operation
⋅ When the motor is operated at 60Hz (or 50Hz), more efficient operation can be performed by the commercial power
supply than by the inverter. When the motor cannot be stopped for a long time for the maintenance/inspection of the
inverter, it is recommended to provide the commercial power supply circuit.
⋅ To switch between inverter operation and bypass operation, an interlock must be provided to stop the motor once
and then start it by the inverter in order to prevent the inverter from resulting in an overcurrent alarm. Using the
electronic bypass sequence function that outputs the timing signal for operation of the magnetic contactor, a
complicated commercial power supply switchover interlock can be provided by the inverter.
CAUTION
Commercial operation can not be performed with the Mitsubishi vector motor (SF-V5RU).
Initial
Setting Range
Value
⋅ 1.5K or less ....................................................... 0.5s,
⋅ 2.2K to 7.5K or less
0
⋅ 11K to 55K or less
⋅ 75K or more ...................................................... 5.0s,
The above times are coasting time.
9999
55K or
0.1 to
less
5s
Set the waiting time for inverter-triggered restart after an
instantaneous power failure.
75K or
0.1 to
more
30s
9999
No restart
1s
0 to 60s
Set a voltage starting time at restart.
0
Without electronic bypass sequence
0
1
With electronic bypass sequence
1s
0 to 100s
Set the operation interlock time of MC2 and MC3.
Set the time slightly longer (0.3 to 0.5s or so) than the time from
0.5s
0 to 100s
when the ON signal enters MC3 until it actually turns on.
0
Inverter output is stopped (motor coast) at inverter fault.
Operation is automatically switched to bypass operation at
0
1
inverter fault (Not switched when an external thermal error
occurs)
Set the frequency to switch inverter operation to bypass
operation.
Inverter operation is performed from a start until Pr. 139 is
0 to 60Hz
reached, and when the output frequency is at or above Pr.
9999
139, inverter operation is automatically switched to bypass
operation.
9999
Without automatic switchover
Valid during automatic switchover operation (Pr. 139 ≠ 9999)
When the frequency command decreases below (Pr. 139
minus Pr. 159) after operation is switched from inverter
operation to bypass operation, the inverter automatically
0 to 10Hz
switches operation to inverter operation and operates at the
frequency of frequency command. When the inverter start
command (STF/STR) is turned off, operation is switched to
9999
inverter operation also.
Valid during automatic switchover operation (Pr. 139 ≠ 9999)
When the inverter start command (STF/STR) is turned off
9999
after operation is switched from inverter operation to bypass
operation, operation is switched to inverter operation and
the motor decelerates to stop.
Special operation and frequency control
Description
......................................
........................................
Pr. 134
page 341
Pr. 140
page 171
Pr. 158
page 242
Pr. 160
page 293
1s,
3.0s,
4
349

Advertisement

Table of Contents
loading

Table of Contents